FIR06-00745
| FIR-Aging Inspection | 1/25/2007 | 1/25/2007 | 1/26/2007 2:52:26 PM | | NR |
|
|
work is in progress
|
BLD06-03116
| FIRE-Final Inspection | 1/25/2007 | 1/25/2007 | 1/25/2007 4:10:46 PM | P | PASS |
|
|
Life safety finaled.
|
BLD06-00587
| FIRE-Final Inspection | 1/24/2007 | 1/25/2007 | 1/25/2007 3:52:03 PM | P | FAIL |
|
|
No approved plans on site.
|
FIR06-00877
| INSP-Final Inspection | 1/25/2007 | 1/25/2007 | 1/25/2007 3:22:21 PM | P | FAIL |
|
|
Alarm signals as received by the monitoring agency do not match what was sent. Will need to retest.
|
FIR06-00991
| INSP-Final Inspection | 1/25/2007 | 1/25/2007 | 1/25/2007 3:21:43 PM | P | FAIL |
|
|
Alarm signals as received by the monitoring agency do not match what was sent. Will need to retest.
|
BLD06-00587
| FIRE-Alarm Testing | 1/24/2007 | 1/25/2007 | 1/25/2007 2:57:14 PM | A | FAIL |
|
|
No approved plans on site.
|
FIR06-00921
| INSP-Sprinkler Rough-in/Hydro | 1/24/2007 | 1/25/2007 | 1/25/2007 2:56:26 PM | A | CANC |
|
|
Apparently the wrong permit was called in since the contact person did not know about inspection
|
FIR07-00001
| INSP-Final Inspection | 1/22/2007 | 1/25/2007 | 1/25/2007 2:34:32 PM | P | PASS |
|
|
Permit finaled. There was over 22 volts at the EOL
|
BLD06-02304
| FIRE-Final Inspection | 1/24/2007 | 1/25/2007 | 1/25/2007 1:19:23 PM | A | FAIL |
|
|
provide exit sign at the west exit and remove the double interior doors as discussed.
|
FIR06-00815
| INSP-Final Inspection | 1/25/2007 | 1/25/2007 | 1/25/2007 12:58:29 PM | P | PASS |
|
|
permit finaled
|
BLD06-01126
| FIRE-Final Inspection | 1/24/2007 | 1/25/2007 | 1/25/2007 12:46:01 PM | P | PASS |
|
|
life safety finaled
|
FIR06-00972
| INSP-Final Inspection | 1/24/2007 | 1/25/2007 | 1/25/2007 10:27:30 AM | A | PASS |
|
|
The three hood suppression systems operated correctly
|
FIR05-00536
| INSP-Sprinkler Rough-in | 1/24/2007 | 1/25/2007 | 1/25/2007 9:40:22 AM | A | PASS |
|
|
Sprinkler piping in operating rooms 5 through 12 are ok to cover. Also see plans for piping above hardlids in lobby that is ok to cover as well.
|
FIR06-00631
| INSP-Final Inspection | 1/25/2007 | 1/25/2007 | 1/25/2007 9:38:03 AM | P | PASS |
|
|
permit finaled
|
BLD06-00129
| FIRE-Final Inspection | 1/24/2007 | 1/25/2007 | 1/25/2007 9:33:55 AM | A | FAIL |
|
|
The smoke detectors are located too close to the bathroom doors and will need to be relocated and tested.
|
BLD06-00128
| FIRE-Final Inspection | 1/24/2007 | 1/25/2007 | 1/25/2007 9:10:05 AM | A | FAIL |
|
|
The smoke detectors are located too close to the bathroom doors and will need to be relocated and tested.
|
BLD06-00127
| FIRE-Final Inspection | 1/24/2007 | 1/25/2007 | 1/25/2007 9:07:46 AM | A | FAIL |
|
|
The smoke detectors are located too close to the bathroom doors and will need to be relocated and tested.
|