Inspections for the day of: Thursday, January 25, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00745 FIR-Aging Inspection1/25/20071/25/20071/26/2007 2:52:26 PM NR
work is in progress
BLD06-03116 FIRE-Final Inspection1/25/20071/25/20071/25/2007 4:10:46 PMPPASS
Life safety finaled.
BLD06-00587 FIRE-Final Inspection1/24/20071/25/20071/25/2007 3:52:03 PMPFAIL
No approved plans on site.
FIR06-00877 INSP-Final Inspection1/25/20071/25/20071/25/2007 3:22:21 PMPFAIL
Alarm signals as received by the monitoring agency do not match what was sent. Will need to retest.
FIR06-00991 INSP-Final Inspection1/25/20071/25/20071/25/2007 3:21:43 PMPFAIL
Alarm signals as received by the monitoring agency do not match what was sent. Will need to retest.
BLD06-00587 FIRE-Alarm Testing1/24/20071/25/20071/25/2007 2:57:14 PMAFAIL
No approved plans on site.
FIR06-00921 INSP-Sprinkler Rough-in/Hydro1/24/20071/25/20071/25/2007 2:56:26 PMACANC
Apparently the wrong permit was called in since the contact person did not know about inspection
FIR07-00001 INSP-Final Inspection1/22/20071/25/20071/25/2007 2:34:32 PMPPASS
Permit finaled. There was over 22 volts at the EOL
BLD06-02304 FIRE-Final Inspection1/24/20071/25/20071/25/2007 1:19:23 PMAFAIL
provide exit sign at the west exit and remove the double interior doors as discussed.
FIR06-00815 INSP-Final Inspection1/25/20071/25/20071/25/2007 12:58:29 PMPPASS
permit finaled
BLD06-01126 FIRE-Final Inspection1/24/20071/25/20071/25/2007 12:46:01 PMPPASS
life safety finaled
FIR06-00972 INSP-Final Inspection1/24/20071/25/20071/25/2007 10:27:30 AMAPASS
The three hood suppression systems operated correctly
FIR05-00536 INSP-Sprinkler Rough-in1/24/20071/25/20071/25/2007 9:40:22 AMAPASS
Sprinkler piping in operating rooms 5 through 12 are ok to cover. Also see plans for piping above hardlids in lobby that is ok to cover as well.
FIR06-00631 INSP-Final Inspection1/25/20071/25/20071/25/2007 9:38:03 AMPPASS
permit finaled
BLD06-00129 FIRE-Final Inspection1/24/20071/25/20071/25/2007 9:33:55 AMAFAIL
The smoke detectors are located too close to the bathroom doors and will need to be relocated and tested.
BLD06-00128 FIRE-Final Inspection1/24/20071/25/20071/25/2007 9:10:05 AMAFAIL
The smoke detectors are located too close to the bathroom doors and will need to be relocated and tested.
BLD06-00127 FIRE-Final Inspection1/24/20071/25/20071/25/2007 9:07:46 AMAFAIL
The smoke detectors are located too close to the bathroom doors and will need to be relocated and tested.