ELE07-03632
| ELE-Aging Inspection | 1/25/2008 | 1/25/2008 | 1/28/2008 11:07:48 AM | | DONE |
|
|
|
ELE07-03792
| Final | 1/25/2008 | 1/25/2008 | 1/25/2008 3:06:51 PM | P | PASS |
|
|
david Phone #: ###-####
|
ELE07-00102
| Final | 1/25/2008 | 1/25/2008 | 1/25/2008 2:12:53 PM | P | PASS |
|
|
Emmett thinks this was already finaled-angie please call first###-#### Phone #: ###-#### corr. made ok by 432, stopped at site final ok
|
ELE07-03143
| Permanent Service | 1/25/2008 | 1/25/2008 | 1/25/2008 1:35:42 PM | P | FAIL |
|
|
corr. called 110.3(A) replace broken acorn clamp. 250.64(B) protect or replace #8 GEC
|
ELE07-04232
| Final | 1/25/2008 | 1/25/2008 | 1/25/2008 12:52:25 PM | P | PASS |
|
|
hz Phone #: ###-#### ok
|
ELE08-00186
| Electrical Rough-In | 1/24/2008 | 1/25/2008 | 1/25/2008 10:43:13 AM | A | PART |
|
|
This is for Uffer ground inspection. Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa ok
|
ELE07-03998
| Final | 1/24/2008 | 1/25/2008 | 1/25/2008 10:29:53 AM | A | CANC |
|
|
alui Phone #: ###-#### owner needs to be at site and needs r/i not final they will reschedule
|
ELE08-00147
| Permanent Service | 1/24/2008 | 1/25/2008 | 1/25/2008 9:55:49 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS p/s u/g new for meter ok
|
ELE07-03838
| Electrical Rough-In | 1/24/2008 | 1/25/2008 | 1/25/2008 9:23:54 AM | A | FAIL |
|
|
andy Phone #: ###-#### corr. called outlet spacing, nail plates, no screws in plastic boxes secure cables within 12" of panels, use plastic conn. for GEC
|
ELE08-00106
| Final | 1/24/2008 | 1/25/2008 | 1/25/2008 12:00:00 AM | A | CANC |
|
|
daniel Phone #: ###-####
|