BLD03-01020
| FIRE-Final Inspection | 1/24/2008 | 1/25/2008 | 1/30/2008 1:58:15 PM | A | PART |
|
|
Pending verification of a fire alarm supervisory switch at the main control valve for the fire sprinkler system.
|
BLD06-01830
| FIRE-Final Inspection | 1/25/2008 | 1/25/2008 | 1/25/2008 4:27:21 PM | P | FAIL |
|
|
Missing suite address numbers, manual flush bolts at the main entry/exit inactive door leaf are not permitted, need provision to test emergency lighting for functionality.
|
FIR07-00846
| FIR-Aging Inspection | 1/25/2008 | 1/25/2008 | 1/25/2008 4:25:23 PM | | DEFR |
|
|
Work in progress, pending site inspection requests.
|
FIR07-00997
| INSP-Final Inspection | 1/24/2008 | 1/25/2008 | 1/25/2008 3:46:05 PM | A | PART |
|
|
Overhead rough-in inspection only, noted one missing ret. strap, one missing hanger, two overspaced heads at the hard lid ceiling restroom areas, the antifreeze loop piping is not yet tied in to the riser, riser not complete at this time, see approved plan set for annotations, hydrostatic testing not ready due to start pressure well below 200psi., remainder of OH rough-in is acceptable.
|
BLD06-03584
| FIRE-Final Inspection | 1/22/2008 | 1/25/2008 | 1/25/2008 2:56:42 PM | A | FAIL |
|
|
EAS per plan documents is not complete at this time, emergency lighting and exit signage tested okay, need to post one PFE on the wall within travel distances on the second floor as discussed.
|
BLD06-00456
| FIRE-Final Inspection | 1/24/2008 | 1/25/2008 | 1/25/2008 1:16:16 PM | A | NR |
|
|
Need project related fire alarm and sprinkler permit final inspections and approvals prior to building life safety final.
|
BLD07-02928
| FIRE-Final Inspection | 1/24/2008 | 1/25/2008 | 1/25/2008 1:10:00 PM | A | FAIL |
|
|
Need to adjust alarm notification coverage due to overspacing caused by wall removal, finishes are not complete, two existing SD have had bases removed due to construction in progress.
|
BLD07-02755
| FIRE-Final Inspection | 1/24/2008 | 1/25/2008 | 1/25/2008 1:07:24 PM | A | NR |
|
|
Project is not in condition for final life safety due to finishes underway, provide ceiling patch at the dry system riser room, need fire alarm as-built plans as discussed, EM lights and exit signs tested okay.
|
FIR07-00947
| INSP-Final Inspection | 1/24/2008 | 1/25/2008 | 1/25/2008 1:04:46 PM | A | PART |
|
|
Need as-built plans reflecting field modifications, need to relocate SD above the dry system riser away from the air diffuser or relocate grill, provide one additonal strobe at the basement area remodel (attatched project related building permits BLD07-02928) okay to include on this alarm permit as discussed.
|