Inspections for the day of: Friday, January 25, 2008.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00874 INSP-Sprinkler Rough-in1/24/20081/25/20081/25/2008 4:46:53 PMPFAIL
Todays inspection was for the wet system. I failed it because the plans and hydraulic calculations state the max spacing is to be 196sq ft per head. The installation and the piping plans show the heads at nearly 225sq. ft. I contacted Brian. The plans need to be resubmitted prior to the next inspection for verification that the greater spacing is hydraulically supported.
BLD07-03101 FIRE-Final Inspection1/24/20081/25/20081/25/2008 4:44:24 PMAFAIL
Inspection was actually for cover. Two sprinkler pendants were overspaced. I received a phone call from rick with treasure valley fire stating the problem had been fixed. I gave the general contractor permission to cover the remaining areas.
FIR07-00579 INSP-Sprinkler Rough-in1/24/20081/25/20081/25/2008 4:42:46 PMAPASS
The sprinkler rough-in for the gymnasium is passed. See the plans for the areas to the south of the gym that were inspected. The piping above the mechanical mezzanine was not inspected due to time constraints.
BLD07-02645 FIRE-Final Inspection1/24/20081/25/20081/25/2008 1:06:44 PMAFAIL
The door hardware on the office doors does not unlock in a single motion. All other items are ok. Per the mechanical contractor the hvac unit is under 2000cfm.
BLD08-00046 FIRE-Final Inspection1/24/20081/25/20081/25/2008 11:53:22 AMAPASS
life safety passed
BLD07-01359 FIRE-Final Inspection1/24/20081/25/20081/25/2008 10:21:19 AMAPASS
Life safety passed.