Inspections for the day of: Monday, January 25, 2010.
Number of inspections: 11
Percentage of inspections complete: 91 %
Percentage of inspections not complete: 9 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-02159 BLD-Final1/25/20101/25/20101/25/2010 5:01:29 PMPPASS
Fire life safety is satisfactory with the exception of door hardware to be replaced at one storage room- to be verified by structural inspector prior to permit final as discussed.
BLD09-02041 BLD-Final1/25/20101/25/20101/25/2010 4:59:17 PMPPASS
Fire life safety inspection passed.
FIR09-00706 INSP-Final Inspection1/25/20101/25/20101/25/2010 4:58:31 PMPPASS
Corrections verified for completion, final walkthrough passed, fire sprinkler permit finaled.
FIR09-00679 INSP-Final Inspection1/25/20101/25/20101/25/2010 4:54:10 PMPPASS
Fire alarm permit final approved.
FIR09-00737 INSP-Final Inspection1/25/20101/25/20101/25/2010 4:53:34 PMPPASS
Fire alarm permit final approved.
FIR10-00034 INSP-Final Inspection1/22/20101/25/20101/25/2010 4:41:59 PMPPASS
Fire alarm work passed field testing, permit finaled. Door closure to be adjusted and verified for correct sequence at project related building permit final inspection.
BLD10-00086 FIRE-Final Inspection1/25/20101/25/20101/25/2010 12:50:33 PMPPASS
Fire life safety inspection completed satisfactory.
MIS10-00013 FIR-Final1/22/20101/25/20101/25/2010 12:48:43 PMAPART
Correction items include the following: Provide suite address numbers for spaces 110 and 130, max. height for fire extinguishers is 48" AFF, install missing escutcheons at fire sprinklers heads at various locations throughout, replace missing ceiling tile at the closet behind the sound booth, fire sprinklers at three storage rooms are overspaced- note; this work will require an FIR permit and to be performed by a licensed fire protection contractor, spacing for floor mounted obstructions at the stage area to meet NFPA 13 ch. 8 guidelines, provide a current certification for the existing type one hood suppression system in suite 130, provide approved hardware at the main entry/exit door from suite 130.
BLD08-01352 FIRE-Final Inspection1/25/20101/25/20101/25/2010 12:36:15 PMPPASS
Correction verified for completion, fire life safety passed.
BLD08-01352 FIRE-Final Inspection1/22/20101/25/20101/25/2010 12:34:54 PMAPART
Fire life safety is acceptable pending hardware at the new door is corrected to operate under any condition from the egress side.
FIR09-00675 INSP-Final Inspection1/22/20101/25/2010 A 
trent Phone #: ###-####