BLD08-01682
| FIRE-Final Inspection | 1/25/2010 | 1/25/2010 | 1/25/2010 3:45:04 PM | P | PASS |
|
|
Life safety passed.
|
FIR09-00707
| INSP-Sprinkler Rough-in | 1/25/2010 | 1/25/2010 | 1/25/2010 3:20:37 PM | P | CANC |
|
|
Cancel this inspection per Jeremy since work was not complete. Plans were just issued today but an early start agreement was issued on 12-28-2009.
|
BLD09-01808
| FIRE-Final Inspection | 1/22/2010 | 1/25/2010 | 1/25/2010 2:50:43 PM | A | CANC |
|
|
Cancelled by Jerry and rescheduled for wednesday.
|
BLD10-00085
| FIRE-Final Inspection | 1/25/2010 | 1/25/2010 | 1/25/2010 2:49:38 PM | P | FAIL |
|
|
Provide sticker over the main exit door, provide single action hardware of the secondary front exit door, repair all of the exit signs and emergency lights and provide final inspection/pass of the fire alarm permit for the sprinkler monitoring system.
|
BLD09-02293
| FIRE-Final Inspection | 1/25/2010 | 1/25/2010 | 1/25/2010 1:13:05 PM | P | PART |
|
|
life safety passed.
|
FIR09-00735
| INSP-Sprinkler Rough-in | 1/22/2010 | 1/25/2010 | 1/25/2010 11:41:30 AM | A | PASS |
|
|
Sprinkler piping is ok to cover
|
BLD08-01426
| FIRE-Final Inspection | 1/21/2010 | 1/25/2010 | 1/25/2010 11:04:18 AM | A | PASS |
|
|
Life safety passed.
|
FIR09-00708
| INSP-Conference | 1/22/2010 | 1/25/2010 | 1/25/2010 9:14:26 AM | A | DONE |
|
|
Sprinkler pendant locations in relationship to pendant lights came into question. Per NFPA 13 and discussion with Tim Frost, the pendant lights will not be an issue.
|
BLD09-02293
| FIRE-Final Inspection | 1/22/2010 | 1/25/2010 | 1/25/2010 9:06:42 AM | A | FAIL |
|
|
The east door exit sign did not operate and the thumb turn lock needs to be removed from the rear exit door now that approved hardware has been installed.
|