Inspections for the day of: Monday, January 25, 2016.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00217 Electrical Rough-In1/25/20161/25/20161/25/2016 3:32:12 PMPPASS
Please call to gain access. Thank you Phone #: ###-#### Inspection requested via web by Eric Brown
Kitchen remodel and cans in family room rough in ok cover
ELE16-00111 Final1/25/20161/25/20161/25/2016 2:47:42 PMPPASS
200 amp manufactured home Phone #: ###-#### Inspection requested via web by jamie berg Final ok
ELE16-00203 Electrical Rough-In1/25/20161/25/20161/25/2016 1:58:31 PMPPASS
underground // Jose Phone #: ###-####
Discussed the route for service entrance conductors for fire pump. Due to route outside of building will set a traffic rated concrete pull box in ground about center of south side near walkway. Conductors to be over sized for voltage drop. Path across ramp to be encased in concrete for traffic on ramp. Underground from south east corner to mid way on ramp only rough in ok cover
ELE15-03958 Permanent Service1/25/20161/25/20161/25/2016 12:56:54 PMAPASS
Re-inspect gear Phone #: ###-#### Inspection requested via web by Thomas Jenkins p/s o/h rec ok
ELE15-03958 Electrical Rough-In1/25/20161/25/20161/25/2016 12:56:39 PMPPASS
Re-inspect gear Phone #: ###-#### Inspection requested via web by Thomas Jenkins Walls and hard lids in front offices, locker room not ready, main floor as noted on print. Rough in ok cover
MIS16-00016 BLD-Final1/25/20161/25/20161/25/2016 10:36:59 AMPCANC
as per Rock See ELE notes
MIS16-00016 ELE-Conference1/25/20161/25/20161/25/2016 10:36:22 AMPFAIL
as per Rock
Shop wired with out permits.
400.8- Flexible cords shall not be used as substitute for fixed wiring.
400.8- Flexible cord shall not be installed in walls, or ran through floors, or ceilings.
210.8- All 120 volt 15 and 20 amp receptacle outlets shall have GFCI protection.
Date on 12-2 NM cable 10-10-2012.
7 days to secure permit for shop electrical and call for preliminary conference to discuss.
ELE15-03818 Final1/21/20161/25/20161/25/2016 10:10:45 AMAFAIL
Call George before hand to meet on job site. Phone #: ###-#### Inspection requested via web by Shannon Wall
250.32- Grounding electrode conductor shall not be connected to grounded conductor on load side of service at shop.
ELE15-03503 Final1/22/20161/25/20161/25/2016 9:01:29 AMAPASS
Garage code is 6767 Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok