Inspections for the day of: Friday, January 25, 2019.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02181 Final1/24/20191/25/20191/25/2019 2:31:42 PMPFAIL
Phone #: ###-#### Inspection requested via web by Bryan Atkins
110.3- GFCI on north wall will not trip.
210.8- Single phase up to 50 amp and 3- phase receptacles up to 100 amp 150 volts to ground or less shall have GFCI protection. Welder and plasma.
330.30- MC cable shall be secured with in 12" of boxes other than fixture whips. North door opener.
400.5- 6-3 flexible cords with 3 current carrying conductors ampacity shall not exceed 45 amps. Welder and plasma.
400.12- Flexible cords shall not be run thru walls, floors, or ceilings. Remove temp lighting cords and one cord from level 1 to mezz for fan.
ELE18-02894 Final1/24/20191/25/20191/25/2019 10:21:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Robert Carter
Corrections made. Final ok
ELE19-00300 Temporary Service1/24/20191/25/20191/25/2019 9:37:52 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
ELE19-00293 Temporary Service1/24/20191/25/20191/25/2019 9:04:52 AMAPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt t/s u/g n ok
ELE18-04727 Electrical Rough-In1/24/20191/25/20191/25/2019 8:33:39 AMAPASS
Ceiling Inspection, Chad VanOrden is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Grid rough in ok cover