FIR03-00523
| INSP-Sprinkler Rough-in | 1/23/2004 | 1/26/2004 | 1/26/2004 12:00:00 AM | A | PART |
|
|
fire smoke dampers operated manually (service switches) Ok. Fire alarm not complete yet 1/26/2004 11:13:03 AM
|
MIS04-00016
| FIR-Final | 1/23/2004 | 1/26/2004 | 1/26/2004 12:00:00 AM | A | FAIL |
|
|
Jay Blacker ###-#### Provide annual inspection for the two fire extinguishers, provide the missing canopies on the sprinkler pendants and repair emergency lights 1/26/2004 9:27:31 AM
|
FIR03-00388
| INSP-Alarm Testing | 1/21/2004 | 1/26/2004 | 1/26/2004 12:00:00 AM | A | PASS |
|
|
Fire alarm finaled 1/26/2004 9:08:46 AM
|
BLD03-00379
| FIRE-Final Inspection | 1/26/2004 | 1/26/2004 | 1/26/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled
|
BLD03-00798
| FIRE-Final Inspection | 1/26/2004 | 1/26/2004 | 1/26/2004 12:00:00 AM | P | PASS |
|
|
fire alarm and fire life safety finaled 1/26/2004 3:10:05 PM
|
FIR03-00628
| INSP-Sprinkler Rough-in/Hydro | 1/26/2004 | 1/26/2004 | 1/26/2004 12:00:00 AM | P | PART |
|
|
above ground hydro test on the anti-freeze loop is ok. Drain pipe on the exterior of the building needs to be protected from corrosion per NFPA 13 and the tamper switches need to be monitored by the fire alarm system 1/26/2004 3:53:49 PM
|
BLD03-02539
| FIRE-Final Inspection | 1/22/2004 | 1/26/2004 | 1/26/2004 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 1/26/2004 1:28:55 PM
|
BLD04-00030
| FIRE-Final Inspection | 1/23/2004 | 1/26/2004 | 1/26/2004 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 1/26/2004 1:31:13 PM
|
FIR03-00379
| INSP-Final Inspection | 1/23/2004 | 1/26/2004 | 1/26/2004 12:00:00 AM | P | CANC |
|
|
Permit voided. This work was not to be done. 1/26/2004 1:27:47 PM
|