BLD04-01480
| FIRE-Final Inspection | 1/26/2005 | 1/26/2005 | 1/26/2005 11:06:04 AM | P | CANC |
|
|
AS LATE AS POSIBLE TODAY; Phone #: ###-#### Internet Inspection Request from: David Mortensen Inspection cancelled from web by: David Mortensen
|
BLD04-00838
| FIRE-Final Inspection | 1/25/2005 | 1/26/2005 | 1/26/2005 12:00:00 AM | A | PART |
|
|
A temporary occupancy was given with dave millers permission. Items needing to be corrected are: Label duct smoke detectors for hvac unit location, install fourth annunciator, provide two additional fire extinguishers, provide three remaining fire dampers in the returns and provide the foam filters for the sample tubes for duct detector #3. 1/26/2005 11:02:55 AM
|
FIR04-00656
| INSP-Sprinkler Rough-in/Hydro | 1/25/2005 | 1/26/2005 | 1/26/2005 12:00:00 AM | A | PART |
|
|
See approved plans for location on fourth floor that is ok for covering. Plans need to be resubmitted again to get approval for the piping changes at the south end of the building and the different heads in the overbuilds. 1/26/2005 11:00:34 AM
|
FIR04-00582
| INSP-Final Inspection | 1/26/2005 | 1/26/2005 | 1/26/2005 12:00:00 AM | P | PASS |
|
|
fire sprinkler finaled 1/26/2005 4:48:38 PM
|
BLD04-01480
| FIRE-Final Inspection | 1/26/2005 | 1/26/2005 | 1/26/2005 12:00:00 AM | P | FAIL |
|
|
Gary; ###-#### The remote annunciators for the duct smoke detectors have not been installed yet and the exit discharge lighting was not finished either. For final test duct detectors and annunciators, emergency lighting/exit signs including exit discharge and door hardware is incorrect in the dining area. Only one door can have the key locking hardware. Air balance reports, hood and fire extinguishers are ok. 1/26/2005 2:30:06 PM
|