Inspections for the day of: Thursday, January 26, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03895 Rough-In Permanent Service1/25/20061/26/20061/26/2006 4:07:38 PMPPART
mark --call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
grounds not made up and panel not bonded
U/G Ok to cover
ELE05-02930 Final1/25/20061/26/20061/26/2006 3:16:42 PMPPASS
Scheduled by a contractor via Hello! on 1/25/2006 at 10:38:38 AM. Contact: ###-####.
ELE06-00308 Final1/26/20061/26/20061/26/2006 2:17:54 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
no water bond.
use plastic romex connectror on GEC
ELE05-04364 Rough-In Permanent Service1/26/20061/26/20061/26/2006 2:03:17 PMPPASS
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
P/S U/G N Ok
ELE06-00220 Electrical Rough-In1/26/20061/26/20061/26/2006 1:25:57 PMPPASS
Mark; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
misc walls ok
ELE06-00014 Final1/25/20061/26/20061/26/2006 1:25:20 PMPPASS
###-#### please call 1/2hr before for access; Phone #: ###-#### Internet Inspection Request from: Heather Packer
ELE05-04610 Permanent Service1/25/20061/26/20061/26/2006 10:50:30 AMANH
###-####
no access
ELE05-04586 Electrical Rough-In1/25/20061/26/20061/26/2006 10:21:48 AMAPART
John - for wall cover insp; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
walls ok
service not ready. isolate neutral check LB listing instructions and strap conduit
ELE05-03117 Final1/25/20061/26/20061/26/2006 10:18:36 AMAPASS
reegan ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
ELE05-04585 Permanent Service1/25/20061/26/20061/26/2006 8:54:13 AMAFAIL
Scheduled by a contractor via Hello! on 1/25/2006 at 12:25:16 PM. Contact: ###-####.
strap pvc. bond nipple between ct can and 600a panelboard. tap external for GEC also proper connectors either plastic Romex or listed for GEC. provide light and a way to use power.