FIR04-00490
| INSP-Sprinkler Rough-in/Hydro | 1/23/2006 | 1/23/2006 | | A | |
|
|
Check for completion.
|
FIR05-00425
| INSP-Sprinkler Rough-in/Hydro | 1/25/2006 | 1/26/2006 | 1/26/2006 5:34:39 PM | P | CANC |
|
|
Inspection for the fire pump flow test canceled due to lack of approved plans for the pump and the associated secondary supply tank approvals.
|
BLD05-01714
| FIRE-Final Inspection | 1/25/2006 | 1/26/2006 | 1/26/2006 5:08:16 PM | P | PASS |
|
|
Fire life safety is acceptable, inspection passed.
|
FIR05-00414
| INSP-Final Inspection | 1/26/2006 | 1/26/2006 | 1/26/2006 5:03:58 PM | P | PASS |
|
|
Overhead fire sprinkler work passed final inspection.
|
BLD05-03045
| FIRE-Final Inspection | 1/25/2006 | 1/26/2006 | 1/26/2006 2:43:52 PM | A | PASS |
|
|
Life safety is satisfactory for the vanilla finish, fire sprinkler modifications are addressed under the TI permit.
|
FIR06-00029
| INSP-Final Inspection | 1/24/2006 | 1/26/2006 | 1/26/2006 1:03:05 PM | A | PASS |
|
|
The hood suppression system operated correctly under test conditions, one partialy obstructed nozzle was cleaned and replaced while on site. Inspection passsed.
|
BLD05-02334
| FIRE-Final Inspection | 1/25/2006 | 1/26/2006 | 1/26/2006 11:39:39 AM | A | FAIL |
|
|
Provide an additional fire extinguisher for the great room/kitchen and lobby area as the distance to the nearest extinguisher from these spaces exceeds maximum travel allowed, provide approved hardware at the FACP room door, provide approved hardware at the pool enclosure gate meeting IFC 2003 1008.1.8.2 for height requirements.
|