Inspections for the day of: Thursday, January 26, 2006.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00312 INSP-Sprinkler Rough-in1/25/20061/26/20061/26/2006 4:56:21 PMPPASS
Sprinkler piping in the second floor attic and the east tenant improvement space are ok for cover
FIR05-00596 INSP-Sprinkler Rough-in1/25/20061/26/20061/26/2006 3:27:11 PMAPASS
Three lengths of 6" underground supply piping have been installed along the face of the building. They are ok for cover.
MIS06-00018 FIR-Final1/25/20061/26/20061/26/2006 12:44:52 PMAPART
Remove the thumbturn lock. Keyed lock is ok. Provide sticker at exit. Provide fire extinguisher with tag and provide suite number.
FIR05-00858 INSP-Final Inspection1/25/20061/26/20061/26/2006 11:30:48 AMAFAIL
No final inspection until the ceiling tile is installed. Ceiling tile is ok to be installed and the piping covered.
BLD05-02069 FIRE-Final Inspection1/25/20061/26/20061/26/2006 10:45:39 AMAFAIL
Fire alarm modifications are required as per review comment #18, need to test exit lights and emergency lights
FIR05-00768 INSP-Final Inspection1/18/20061/26/20061/26/2006 10:43:06 AMAFAIL
Provide holes around the duct detector housings, provide differential test for the roof mounted duct detectors since they are mounted in 90's, test unit that was not working in the flower shop