ELE06-02779
| ELE-Aging Inspection | 1/26/2007 | 1/26/2007 | 1/26/2007 3:20:30 PM | | DONE |
|
|
|
ELE06-02779
| Final | 1/26/2007 | 1/26/2007 | 1/26/2007 3:20:14 PM | P | PASS |
|
|
sign labeled and listed
|
ELE07-00046
| Electrical Rough-In | 1/26/2007 | 1/26/2007 | 1/26/2007 3:19:43 PM | P | FAIL |
|
|
Reinspection for underground only. If you have any questions please call Marvin Miller. Thank you. Phone #: ###-#### corrections not made shall not have more than 360 degrees tatal bends in raceway as noted in prior inspection in the AM called note all raceways
|
ELE07-00274
| Temporary Service | 1/26/2007 | 1/26/2007 | 1/26/2007 2:26:07 PM | P | FAIL |
|
|
CONTACT: CASEY WILDE Phone #: ###-#### corr. called remove romex conn for GEC use plastic, 110.12(A) seal all unused KOs, 590.6(B)(1) needs gfci for 220V recdept cord cap, 408.41 only 1 neutral per terminal
|
ELE06-03027
| Final | 1/25/2007 | 1/26/2007 | 1/26/2007 1:44:55 PM | P | FAIL |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall on prior inspection tlked with contr about meyal raceway in nonmetallic enclosure 314.3 explained the requirements of NEC and manufactures instructions, violation not made no final
|
ELE07-00143
| Final | 1/25/2007 | 1/26/2007 | 1/26/2007 1:33:47 PM | P | FAIL |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall not ready
|
ELE06-04586
| Electrical Rough-In | 1/26/2007 | 1/26/2007 | 1/26/2007 12:59:09 PM | P | FAIL |
|
|
ceiling inspection. If any way it could be done in the morning it would be appreciated. Thank you Phone #: ###-#### corr. posted for high and low voltage, high V 110.12(A) seal all KOs, install covers all boxes, low V 800.21&24, 830.21&24 remove cables that lay on grid and support and secure, same for stat and other hvac wiring
|
ELE07-00094
| Permanent Service | 1/26/2007 | 1/26/2007 | 1/26/2007 12:30:20 PM | P | PASS |
|
|
re-inspection of grounding Phone #: ###-#### p/s u/g new ok
|
ELE06-04530
| Final | 1/26/2007 | 1/26/2007 | 1/26/2007 11:44:42 AM | A | FAIL |
|
|
Please call for accessand let me know if there are any problems. Thank You. Kevin Phone #: ###-#### corr. called 408.4 panel directory, 210.8 gfci left of kit and garage bad
|
ELE06-04392
| Final | 1/25/2007 | 1/26/2007 | 1/26/2007 10:24:28 AM | A | PASS |
|
|
call 1st ###-#### ok
|
ELE07-00234
| Temporary Service | 1/25/2007 | 1/26/2007 | 1/26/2007 10:08:51 AM | A | PASS |
|
|
Phone #: ###-#### t/s u/g new ok
|
ELE06-02206
| Final | 1/25/2007 | 1/26/2007 | 1/26/2007 9:50:13 AM | A | PASS |
|
|
todd Note: please call 1/2 hr prior; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok owner needs inuse cover. he will install and call me
|
ELE07-00278
| Conference | 1/25/2007 | 1/26/2007 | 1/26/2007 9:38:08 AM | A | DONE |
|
|
paul ralph-- ###-#### owner did work 6 years ago no permit or inspections shall uncover all wiring, and wire to current NEC
|
ELE06-02704
| Electrical Rough-In | 1/25/2007 | 1/26/2007 | 1/26/2007 9:02:55 AM | A | PART |
|
|
Please inspect rough-in at C-wing. Thank you. Phone #: ###-#### c wing 1st floor all rooms walls and ceiling corridor walls
|
ELE06-04392
| ELE-Aging Inspection | 1/25/2007 | 1/26/2007 | 1/25/2007 7:56:59 AM | A | CANC |
|
|
call ###-####
|