Inspections for the day of: Friday, January 26, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02779 ELE-Aging Inspection1/26/20071/26/20071/26/2007 3:20:30 PM DONE
ELE06-02779 Final1/26/20071/26/20071/26/2007 3:20:14 PMPPASS
sign labeled and listed
ELE07-00046 Electrical Rough-In1/26/20071/26/20071/26/2007 3:19:43 PMPFAIL
Reinspection for underground only. If you have any questions please call Marvin Miller. Thank you.
Phone #: ###-#### corrections not made shall not have more than 360 degrees tatal bends in raceway as noted in prior inspection in the AM called note all raceways
ELE07-00274 Temporary Service1/26/20071/26/20071/26/2007 2:26:07 PMPFAIL
CONTACT: CASEY WILDE Phone #: ###-#### corr. called remove romex conn for GEC use plastic, 110.12(A) seal all unused KOs, 590.6(B)(1) needs gfci for 220V recdept cord cap, 408.41 only 1 neutral per terminal
ELE06-03027 Final1/25/20071/26/20071/26/2007 1:44:55 PMPFAIL
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall on prior inspection tlked with contr about meyal raceway in nonmetallic enclosure 314.3 explained the requirements of NEC and manufactures instructions, violation not made no final
ELE07-00143 Final1/25/20071/26/20071/26/2007 1:33:47 PMPFAIL
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall not ready
ELE06-04586 Electrical Rough-In1/26/20071/26/20071/26/2007 12:59:09 PMPFAIL
ceiling inspection. If any way it could be done in the morning it would be appreciated. Thank you Phone #: ###-#### corr. posted for high and low voltage, high V 110.12(A) seal all KOs, install covers all boxes, low V 800.21&24, 830.21&24 remove cables that lay on grid and support and secure, same for stat and other hvac wiring
ELE07-00094 Permanent Service1/26/20071/26/20071/26/2007 12:30:20 PMPPASS
re-inspection of grounding Phone #: ###-#### p/s u/g new ok
ELE06-04530 Final1/26/20071/26/20071/26/2007 11:44:42 AMAFAIL
Please call for accessand let me know if there are any problems. Thank You. Kevin Phone #: ###-#### corr. called 408.4 panel directory, 210.8 gfci left of kit and garage bad
ELE06-04392 Final1/25/20071/26/20071/26/2007 10:24:28 AMAPASS
call 1st ###-#### ok
ELE07-00234 Temporary Service1/25/20071/26/20071/26/2007 10:08:51 AMAPASS
Phone #: ###-#### t/s u/g new ok
ELE06-02206 Final1/25/20071/26/20071/26/2007 9:50:13 AMAPASS
todd Note: please call 1/2 hr prior; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok owner needs inuse cover. he will install and call me
ELE07-00278 Conference1/25/20071/26/20071/26/2007 9:38:08 AMADONE
paul ralph-- ###-#### owner did work 6 years ago no permit or inspections shall uncover all wiring, and wire to current NEC
ELE06-02704 Electrical Rough-In1/25/20071/26/20071/26/2007 9:02:55 AMAPART
Please inspect rough-in at C-wing. Thank you. Phone #: ###-#### c wing 1st floor all rooms walls and ceiling corridor walls
ELE06-04392 ELE-Aging Inspection1/25/20071/26/20071/25/2007 7:56:59 AMACANC
call ###-####