Inspections for the day of: Friday, January 26, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03989 ELE-Aging Inspection1/26/20071/26/20072/2/2007 2:48:46 PM DONE
see final
ELE06-04269 Final1/25/20071/26/20071/26/2007 3:51:42 PMPNH
Phone #: ###-#### called, left card
ELE06-02716 Electrical Rough-In1/26/20071/26/20071/26/2007 3:30:35 PMPPASS
ceiling inspection please...james; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt ok to cover ceilings, left card stating need to see lv before tiles installed
ELE07-00249 Electrical Rough-In1/26/20071/26/20071/26/2007 2:39:05 PMPPASS
Ready for inspection. Tech/Dan ###-#### Phone #: ###-#### ric ok, ok to rec p/s, see final
ELE07-00249 Final1/26/20071/26/20071/26/2007 2:37:59 PMPPASS
Ready for inspection. Tech/Dan ###-#### Phone #: ###-#### ok to final
ELE07-00114 Permanent Service1/26/20071/26/20071/26/2007 1:43:55 PMPPASS
For questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty Phone #: ###-#### p/s u/g rec ok
ELE07-00167 Rough-In Permanent Service1/24/20071/26/20071/26/2007 1:09:42 PMPNR
Contact is Bob Phone #: ###-#### met elect, reviewed service, told to open u/g to garage, wall space and plan change, box fill, broken box, and grounding to service
ELE07-00174 Rough-In Permanent Service1/24/20071/26/20071/26/2007 1:06:21 PMPNR
Contact is Bob Phone #: ###-#### met elect, reviewed gndg for service, told about garage door lights,layout of walls, told to open up u/g to garage
ELE07-00265 Temporary Service1/25/20071/26/20071/26/2007 10:41:30 AMAFAIL
Phone #: ###-#### called, left corr notice, nec 250.24 gec shall be connected to grounded service conductor, 110.3 shall not use 2 hole connector for abrasion protection (dis-similar metals),not listed
ELE06-04433 Electrical Rough-In1/25/20071/26/20071/26/2007 10:14:53 AMAPART
contact: Jason Martineau - ceiling inspection Phone #: ###-#### ok to occupy break room, clg cover ok and t/o for room 109
ELE06-03988 Final1/26/20071/26/20071/26/2007 9:51:29 AMPPASS
looked at sign, ok to final
ELE06-03784 Final1/25/20071/26/20071/26/2007 9:27:02 AMAPASS
eddie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr to install water heater disconnects, ok to final
ELE07-00046 Electrical Rough-In1/25/20071/26/20071/26/2007 9:20:57 AMAFAIL
This will be for underground only. If you have any questions please call Marv Miller. Thank you. Phone #: ###-#### called left corr notice, nec 352.26 there shall not be over 360 degree bends in raceway
ELE06-03829 Final1/25/20071/26/20071/26/2007 8:37:51 AMAPASS
Requesting a final inspection. Phone #: ###-#### corr made, ok to final