Inspections for the day of: Friday, January 26, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00408 FIR-Aging Inspection1/26/20071/26/20071/30/2007 9:29:56 AM DEFR
FIR05-00425 INSP-Sprinkler Rough-in/Hydro1/26/20071/26/20071/26/2007 4:14:18 PMPPART
Begin 72 hr. tank hydro test @ 2:40 pm (37" to water line).
FIR07-00004 INSP-Sprinkler Rough-in/Hydro1/25/20071/26/20071/26/2007 4:12:00 PMAFAIL
Noted locations on approved plan set which are in need of revision including missing head placement and obstructed heads.
FIR06-00948 INSP-Sprinkler Rough-in/Hydro1/25/20071/26/20071/26/2007 3:52:39 PMAPART
OH install is good for cover.
FIR06-00995 INSP-Sprinkler Rough-in1/25/20071/26/20071/26/2007 1:58:27 PMPPART
Overhead fire sprinkler install is approved for cover.
BLD06-03581 FIRE-Final Inspection1/26/20071/26/20071/26/2007 1:45:17 PMPPASS
Fire life safety passed field inspection.
BLD06-01083 FIRE-Final Inspection1/26/20071/26/20071/26/2007 1:20:51 PMAPASS
Fire life safety is satisfactory, inspection passed.
FIR06-00092 INSP-Final Inspection1/26/20071/26/20071/26/2007 1:18:29 PMAPASS
Fire sprinkler final inspection passed, permit finaled.
FIR06-00715 INSP-Final Inspection1/26/20071/26/20071/26/2007 12:23:11 PMPPART
Verified elevator voltage monitor and waterflow alarm, permit final pending completion of work scope for the 3rd floor.
FIR07-00011 INSP-Sprinkler Rough-in1/25/20071/26/20071/26/2007 12:20:39 PMAPART
Inspection for cover at the drop ceiling areas as marked on approved plans is approved.
BLD06-01745 FIRE-Final Inspection1/25/20071/26/20071/26/2007 11:28:29 AMAPASS
Fire life safety is acceptable, noted two missing 2nd pc. 401 sprinkler canopies to be replaced by contractor as agreed.
FIR06-00973 INSP-Final Inspection1/24/20071/26/20071/26/2007 11:26:45 AMAPASS
Field alarm inspection passed, fire alarm permit finaled.
FIR06-00954 INSP-Final Inspection1/25/20071/26/20071/26/2007 9:49:07 AMAFAIL
Missing head in the riser room, heads at the storage room are overspaced, one head in the NW hall is overspcaed off an adjacent wall, missing hanger on the hallway 1 1/2 grid main, provide sufficient coverage under the stairs at the east side as discussed. The fire sprinklers in the drop ceiling areas are okay for cover.
FIR06-00595 INSP-Alarm Testing1/24/20071/26/20071/26/2007 8:33:57 AMAFAIL
Partial alarm notification testing completed for the 4th floor SE and SW quads and the entire penthouse. Noted two non-functional pull stations and one non-functional strobe at the 4th floor, still need to test the SD in the electrical and telephone rooms, the penthouse is missing one strobe to be added, one a/v is not functional on audio, only one manual pull tested at this time.
FIR06-00814 INSP-Final Inspection1/26/20071/26/20071/26/2007 8:24:42 AMPPASS
Fire sprinkler permit finaled.
FIR06-00644 INSP-Alarm Testing1/25/20071/26/20071/26/2007 8:14:16 AMPCANC
alex - after 2:30p; Phone #: ###-#### Internet Inspection Request from: Victoria Beall Inspection cancelled from web by: Victoria Beall