FIR06-00408
| FIR-Aging Inspection | 1/26/2007 | 1/26/2007 | 1/30/2007 9:29:56 AM | | DEFR |
|
|
|
FIR05-00425
| INSP-Sprinkler Rough-in/Hydro | 1/26/2007 | 1/26/2007 | 1/26/2007 4:14:18 PM | P | PART |
|
|
Begin 72 hr. tank hydro test @ 2:40 pm (37" to water line).
|
FIR07-00004
| INSP-Sprinkler Rough-in/Hydro | 1/25/2007 | 1/26/2007 | 1/26/2007 4:12:00 PM | A | FAIL |
|
|
Noted locations on approved plan set which are in need of revision including missing head placement and obstructed heads.
|
FIR06-00948
| INSP-Sprinkler Rough-in/Hydro | 1/25/2007 | 1/26/2007 | 1/26/2007 3:52:39 PM | A | PART |
|
|
OH install is good for cover.
|
FIR06-00995
| INSP-Sprinkler Rough-in | 1/25/2007 | 1/26/2007 | 1/26/2007 1:58:27 PM | P | PART |
|
|
Overhead fire sprinkler install is approved for cover.
|
BLD06-03581
| FIRE-Final Inspection | 1/26/2007 | 1/26/2007 | 1/26/2007 1:45:17 PM | P | PASS |
|
|
Fire life safety passed field inspection.
|
BLD06-01083
| FIRE-Final Inspection | 1/26/2007 | 1/26/2007 | 1/26/2007 1:20:51 PM | A | PASS |
|
|
Fire life safety is satisfactory, inspection passed.
|
FIR06-00092
| INSP-Final Inspection | 1/26/2007 | 1/26/2007 | 1/26/2007 1:18:29 PM | A | PASS |
|
|
Fire sprinkler final inspection passed, permit finaled.
|
FIR06-00715
| INSP-Final Inspection | 1/26/2007 | 1/26/2007 | 1/26/2007 12:23:11 PM | P | PART |
|
|
Verified elevator voltage monitor and waterflow alarm, permit final pending completion of work scope for the 3rd floor.
|
FIR07-00011
| INSP-Sprinkler Rough-in | 1/25/2007 | 1/26/2007 | 1/26/2007 12:20:39 PM | A | PART |
|
|
Inspection for cover at the drop ceiling areas as marked on approved plans is approved.
|
BLD06-01745
| FIRE-Final Inspection | 1/25/2007 | 1/26/2007 | 1/26/2007 11:28:29 AM | A | PASS |
|
|
Fire life safety is acceptable, noted two missing 2nd pc. 401 sprinkler canopies to be replaced by contractor as agreed.
|
FIR06-00973
| INSP-Final Inspection | 1/24/2007 | 1/26/2007 | 1/26/2007 11:26:45 AM | A | PASS |
|
|
Field alarm inspection passed, fire alarm permit finaled.
|
FIR06-00954
| INSP-Final Inspection | 1/25/2007 | 1/26/2007 | 1/26/2007 9:49:07 AM | A | FAIL |
|
|
Missing head in the riser room, heads at the storage room are overspaced, one head in the NW hall is overspcaed off an adjacent wall, missing hanger on the hallway 1 1/2 grid main, provide sufficient coverage under the stairs at the east side as discussed. The fire sprinklers in the drop ceiling areas are okay for cover.
|
FIR06-00595
| INSP-Alarm Testing | 1/24/2007 | 1/26/2007 | 1/26/2007 8:33:57 AM | A | FAIL |
|
|
Partial alarm notification testing completed for the 4th floor SE and SW quads and the entire penthouse. Noted two non-functional pull stations and one non-functional strobe at the 4th floor, still need to test the SD in the electrical and telephone rooms, the penthouse is missing one strobe to be added, one a/v is not functional on audio, only one manual pull tested at this time.
|
FIR06-00814
| INSP-Final Inspection | 1/26/2007 | 1/26/2007 | 1/26/2007 8:24:42 AM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR06-00644
| INSP-Alarm Testing | 1/25/2007 | 1/26/2007 | 1/26/2007 8:14:16 AM | P | CANC |
|
|
alex - after 2:30p; Phone #: ###-#### Internet Inspection Request from: Victoria Beall Inspection cancelled from web by: Victoria Beall
|