FIR06-00810 INSP-Final Inspection1/26/20071/26/20071/30/2007 3:23:23 PMPPASS
This permit is finaled. One of the two duct smoke detectors has been deleted. Thet hvac unit has been removed from the roof top as requested..
FIR06-00825 INSP-Final Inspection1/26/20071/26/20071/26/2007 4:33:33 PMPFAIL
Inspection was for rough-in. Piping is ok to cover.
FIR07-00082 INSP-Final Inspection1/26/20071/26/20071/26/2007 4:32:33 PMPPART
See the rooms marked on the approved drawings for the piping that is ok to cover. Not all of the work is complete.
FIR07-00060 INSP-Final Inspection1/26/20071/26/20071/26/2007 4:31:18 PMPPASS
Permit finaled
FIR06-00938 INSP-Final Inspection1/26/20071/26/20071/26/2007 3:21:54 PMPCANC
Duplicate inspection
BLD06-02999 FIRE-Final Inspection1/26/20071/26/20071/26/2007 3:11:45 PMPFAIL
Need fire sprinkler permit finaled. Need a permit for the fire alarm work. Need signage for the racks limiting storage to 19'-0".
FIR06-00921 INSP-Final Inspection1/25/20071/26/20071/26/2007 3:06:04 PMPCANC
Not ready for inspection
FIR06-00719 FIR-Aging Inspection1/26/20071/26/20071/26/2007 2:52:46 PM NR
work is in progress
FIR07-00075 INSP-Final Inspection1/26/20071/26/20071/26/2007 2:49:36 PMPPASS
permit finaled
FIR06-00600 INSP-Sprinkler Rough-in1/25/20071/26/20071/26/2007 2:22:24 PMPPASS
Office area sprinkler piping is ok to cover. A flexible coupling is required at the bottom of the feed piping to this area. I will verify at the next inspection
FIR05-00644 INSP-Sprinkler Rough-in/Hydro1/25/20071/26/20071/26/2007 1:49:23 PMPPASS
Hydro test passed. Still need to hydro test the standpipes and 24 hour tests for the dry systems.
FIR07-00067 INSP-Final Inspection1/25/20071/26/20071/26/2007 1:28:12 PMAPASS
permit finaled
FIR07-00075 INSP-Sprinkler Rough-in/Hydro1/25/20071/26/20071/26/2007 1:10:21 PMAPASS
Permit finaled
FIR06-00938 INSP-Sprinkler Rough-in/Hydro1/25/20071/26/20071/26/2007 11:42:35 AMAFAIL
All corrections have been made except there are still problems with the insulation falling and blocking the upright sprinkler heads. Do not cover sprinklers.
FIR06-00921 INSP-Sprinkler Rough-in/Hydro1/25/20071/26/20071/26/2007 11:39:19 AMAPASS
hydro test passed. system held 210 lbs for 2 hours. sprinkler rough-in passed except column protection is required. Also still need tags, signs and forward flush
MIS06-00281 FIR-Final1/25/20071/26/20071/26/2007 10:58:28 AMACANC
Wrong permit number was called in
MIS06-00220 FIR-Final1/26/20071/26/20071/26/2007 10:57:44 AMPPASS
life safety finaled
FIR06-00825 INSP-Sprinkler Rough-in/Hydro1/26/20071/26/20071/26/2007 10:44:48 AMPCANC
Scheduled by a contractor via Hello! on 1/26/2007 at 10:37:17 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jan 26 2007 10:44AM.
BLD05-01261 FIRE-Final Inspection1/26/20071/26/20071/26/2007 10:39:39 AMPPASS
life safety finaled
BLD06-00587 FIRE-Final Inspection1/25/20071/26/20071/26/2007 10:19:53 AMAPASS
life safety finaled
BLD06-02304 FIRE-Final Inspection1/25/20071/26/20071/26/2007 9:33:12 AMAPASS
life safety finaled
FIR06-00877 INSP-Final Inspection1/26/20071/26/20071/26/2007 9:32:42 AMPPASS
permit finaled
FIR06-00991 INSP-Final Inspection1/25/20071/26/20071/26/2007 9:32:01 AMAPASS
Permit finaled