ESC06-01232
| General Inspection | 1/26/2009 | 1/26/2009 | 1/26/2009 4:16:55 PM | P | PASS |
|
|
looked ok, no sign up, essentially done, could final, job taken over by new contractor, rest of permits expired from original contractor
|
ESC08-00700
| General Inspection | 1/26/2009 | 1/26/2009 | 1/26/2009 4:10:00 PM | P | CANC |
|
|
didn't need to go to site, will check at ri
|
ELE08-03237
| Final | 1/26/2009 | 1/26/2009 | 1/26/2009 4:08:58 PM | P | PASS |
|
|
Mike Phone #: ###-####--please call for key information called contractor, ok to final, no esc this project
|
ELE08-03254
| Conference | 1/26/2009 | 1/26/2009 | 1/26/2009 3:24:49 PM | P | DONE |
|
|
darin Note: just a telephone will be fine Phone #: ###-#### talked about conduit in crawl space for commercial building and also mc cable, said conduit supported on grade with supports is ok
|
ESC08-00847
| General Inspection | 1/26/2009 | 1/26/2009 | 1/26/2009 2:54:32 PM | P | PART |
|
|
didn't see sign, parking problem for site, need to park in neighbors driveway, will re-check when go back for corrections
|
ELE08-02584
| Electrical Rough-In | 1/26/2009 | 1/26/2009 | 1/26/2009 2:16:51 PM | P | FAIL |
|
|
robert Phone #: ###-#### met owner, corrections: BCC shall provide all make-up , NEC 210.52 shall provide outlet spacing entering kitchen, no esc this project
|
ELE08-01922
| Final | 1/26/2009 | 1/26/2009 | 1/26/2009 1:41:34 PM | P | PASS |
|
|
Jean Phone #: ###-#### corrections made, ok to final
|
ELE09-00015
| Electrical Rough-In | 1/26/2009 | 1/26/2009 | 1/26/2009 12:32:05 PM | P | FAIL |
|
|
darrin Phone #: ###-#### called left message, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(H) hallway over 10' in length shall have receptacle outlet, BCC all boxes shall be installed and made-up- baths and room adjoining existing house
|
ESC06-01299
| General Inspection | 1/26/2009 | 1/26/2009 | 1/26/2009 9:24:33 AM | A | PASS |
|
|
looked ok
|
ELE07-03307
| Electrical Rough-In | 1/22/2009 | 1/26/2009 | 1/26/2009 8:30:36 AM | A | PASS |
|
|
Contact Neil Ramsey. Rough-in inspection 1st floor ceiling. Also, 6th and 7th floor ceiling inspections. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong 1st floor west soffit and 7th floor ceiling ok to cover
|
ELE09-00125
| Electrical Rough-In | 1/23/2009 | 1/26/2009 | 1/26/2009 12:00:00 AM | A | CANC |
|
|
Please provide wall cover inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean
|