Inspections for the day of: Monday, January 26, 2009.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00626 INSP-Sprinkler Rough-in/Hydro1/26/20091/26/20091/27/2009 2:31:07 PMPPASS
The remaining ceilings covering the sprinkler piping are ok to install
BLD09-00073 FIRE-Final Inspection1/26/20091/26/20091/26/2009 3:37:45 PMPFAIL
Provide an inspection for the fire extinguisher and repair what appears to be a leaking sprinkler pendant.
FIR08-00706 INSP-Sprinkler Rough-in1/26/20091/26/20091/26/2009 3:36:29 PMPPART
The sprinkler rough-in is passed. Not all of the sprinkler drops have been installed. Final sprinkler spacing will need to be verified when drops, ceilings and soffits have been installed. The FDC has been relocated and a sprinkler main in a hydraulic remote area on the north side of the building has been rerouted. These changes will need to be verified by teh plan reviewer.
FIR08-00612 INSP-Final Inspection1/26/20091/26/20091/26/2009 3:18:55 PMPFAIL
The forward flow test passed inspection. The forward flow/FDC assembley did not pass inspection and needs to be installed as per the drawings. Two 3" 90's have been installed at the base of the riser. It appears per the drawings that a very slim safety factor was acheived on remoted area #4. I need verification that the 5% requirement is still satisfied. Ceiling tile needs to be removed where additional hangers were required for the pendant heads. The third floor roof access room needs a ceiling and a pendant, walls to the deck or upright protection needs to be provided throughout the third floor attic space.
BLD07-03134 FIRE-Final Inspection1/23/20091/26/20091/26/2009 2:58:29 PMPCANC
Need the project related fire alarm and fire sprinkler permits finaled first. I also ran out of time for the inspection today.
BLD08-00594 FIRE-Final Inspection1/23/20091/26/20091/26/2009 2:58:02 PMPCANC
Need the project related fire alarm and fire sprinkler permits finaled first. I also ran out of time for the inspection today.
FIR08-00763 INSP-Alarm Testing1/23/20091/26/20091/26/2009 2:49:49 PMPFAIL
All items tested ok except the second floor flow alarm was sent out as a second floor tamper. The first floor electrical room horn was changed to a horn strobe as I waited due to the horn being non temporal.
FIR08-00691 INSP-Final Inspection1/23/20091/26/20091/26/2009 2:05:05 PMAPASS
Permit finaled
FIR08-00636 INSP-Final Inspection1/23/20091/26/20091/26/2009 11:34:05 AMAFAIL
The sprinkler system as installed matched the plans. The problem is that the plans state the maximum storage height is not to exceed 17'0" and it does. The storage appears to be less than 18" from the sprinkler pendants. The product storage needs to be permanantly reduced or the storage height needs to be addressed on the city approved plans.
BLD08-02036 FIRE-Conference1/23/20091/26/20091/26/2009 10:44:32 AMADONE
Scheduled by a contractor via Hello! on 1/23/2009 at 2:13:07 PM. Contact: ###-####.
BLD08-01582 FIRE-Final Inspection1/23/20091/26/20091/26/2009 10:28:07 AMAFAIL
Repair or remove the exit signs, provide stickers at the three exit doors as discussed, provide a tagged fire extinguisher and provide the building address with atleast 4" numbers of a contrasting color.