Inspections for the day of: Tuesday, January 26, 2010.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-02059 ELE-Aging Inspection1/26/20101/26/20101/28/2010 9:51:50 AM DONE
looked at sign, ok to final
ELE08-02826 ELE-Aging Inspection1/26/20101/26/20101/27/2010 3:35:48 PM DONE
no activity, see doc expire
ELE08-02790 ELE-Aging Inspection1/26/20101/26/20101/27/2010 3:32:25 PM DONE
no activity, see doc expire
ELE10-00151 Temporary Service1/26/20101/26/20101/27/2010 8:11:04 AMPFAIL
Dino Phone #: ###-#### called, left correction notice, NEC 250.24 shall connect grounded conductor to grounding electrode conductor via main bonding jumper
ELE09-02159 Electrical Rough-In1/22/20101/26/20101/26/2010 4:01:15 PMPPASS
Please final this permit when you are finished. Owner will give you the tour.
Thanks!!! Dan. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ri ok, no esc this project
ELE09-02159 Final1/26/20101/26/20101/26/2010 4:00:19 PMPPASS
Please final this permit when you are finished. Owner will give you the tour.
Thanks!!! Dan. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final, no esc this project
ESC09-00801 General Inspection1/26/20101/26/20101/26/2010 3:45:15 PMPPASS
looked ok
ESC09-00203 General Inspection1/26/20101/26/20101/26/2010 3:42:45 PMPPASS
looked ok
ELE10-00103 Electrical Rough-In1/26/20101/26/20101/26/2010 3:15:05 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Steve McCloy walls and u/g ok to cover, no esc this project
ELE07-02961 Final1/26/20101/26/20101/26/2010 2:08:03 PMPPASS
John Phone #: ###-#### ok to final, owner moved in, checked available receptacles only, no esc this project
ELE10-00109 Electrical Rough-In1/26/20101/26/20101/26/2010 1:08:39 PMPPASS
underground Phone #: ###-#### Internet Inspection Request from: Daniel Schaffeld ok to cover u/g, reviewed service disconnects and grounding
ELE10-00130 Rough-In Permanent Service1/26/20101/26/20101/26/2010 12:30:15 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Joe Thomas corrections made, ric ok, p/s u/g n ok, no esc this project
ELE09-01997 Electrical Rough-In1/25/20101/26/20101/26/2010 10:07:39 AMAPART
Gene is on-site - ###-####. Middle 10 units and corridor on East side only. Thanks Jack!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ric ok anop
ELE10-00145 Temporary Service1/25/20101/26/20101/26/2010 9:04:40 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Emmet Bushman called, left correction notice- see list for ele10-00144, fee due
ELE10-00144 Temporary Service1/25/20101/26/20101/26/2010 9:02:21 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Emmet Bushman called, left correction notice, same comments ele10-00145, NEC 406.8(B) 15 and 20a non-locking receptacles shall be listed weather resistant type, 312.5 conductors entering enclosures shall be protected from abrasion, 110.12(B) enclosures and equipment shall not be broken or contaminated by foreign materials, 250.53(G) upper end of electrode shall be flush with or below ground, BCC job id sticker shall be posted, address shall be posted, fee due
ELE09-02099 Permanent Service1/25/20101/26/20101/26/2010 8:23:18 AMAPASS
Meter base was changed since service was approved so need new inspection and sticker for IPCO connect. Phone #: ###-#### Internet Inspection Request from: Scott Abbott new meter base, p/s o/h n ok, no esc this project