FIR09-00675
| INSP-Final Inspection | 1/22/2010 | 1/25/2010 | | A | |
|
|
trent Phone #: ###-####
|
FIR09-00607
| FIR-Aging Inspection | 1/26/2010 | 1/26/2010 | 1/26/2010 5:13:10 PM | | DONE |
|
|
Need site inspection request for permit final.
|
FIR09-00472
| INSP-Final Inspection | 1/26/2010 | 1/26/2010 | 1/26/2010 5:12:07 PM | A | PASS |
|
|
Fire sprinkler permit work okayed for final. Inspection completed in conjunction with project related fire alarm testing finished 11/25/09.
|
FIR09-00082
| INSP-Final Inspection | 1/25/2010 | 1/26/2010 | 1/26/2010 5:08:10 PM | A | FAIL |
|
|
Need to provide verification that tamper switches at the pit backflow shutoff valves #1 and 2 are connected to the panel- as FLP wire is disconnected and exposed at a junction box labeled "pit valve os&y" in the riser room. Also need to retest alarm signals as the manual pull station failed to report.
|
FIR09-00016
| INSP-Final Inspection | 1/25/2010 | 1/26/2010 | 1/26/2010 5:02:32 PM | A | PASS |
|
|
Fire alarm testing completed satisfactory, permit finaled.
|
FIR09-00530
| INSP-Final Inspection | 1/25/2010 | 1/26/2010 | 1/26/2010 5:01:50 PM | A | FAIL |
|
|
On site netcon rating reported as 7, at the time of inspection.
|
BLD09-02123
| FIRE-Final Inspection | 1/25/2010 | 1/26/2010 | 1/26/2010 12:23:42 PM | A | PASS |
|
|
Fire life safety inspection passed, corrections completed acceptable, project related fire alarm permit work passed.
|