Inspections for the day of: Tuesday, January 26, 2016.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-04290 FIRE-Final Inspection1/26/20161/26/20161/26/2016 2:47:18 PMPPASS
No fire sprinklers, no fire alarms. Life fire safety passed/complete.
BLD15-04396 FIRE-Final Inspection1/25/20161/26/20161/26/2016 12:38:32 PMPPASS
No fire sprinklers, no fire alarms, fire extinguishers are current. Life fire safety inspection passed/complete.
BLD15-04376 FIRE-Final Inspection1/25/20161/26/20161/26/2016 12:37:34 PMPPASS
No fire sprinklers, no fire alarms, fire extinguishers are current. Life fire safety inspection passed/complete.
BLD15-01841 FIRE-Final Inspection1/26/20161/26/20161/26/2016 12:20:29 PMPPASS
No fire sprinklers, no fire alarms. Core and shell life fire safety passed/complete.
BLD15-01841 FIRE-Sprinkler Rough-in1/26/20161/26/20161/26/2016 12:18:36 PMPCANC
Inspection request not for fire sprinkler rough in, inspection request suppose to be final for life fire safety, canceling this inspection request and generating a new one.
FIR15-00796 INSP-Sprinkler Rough-in/Hydro1/26/20161/26/20161/26/2016 11:42:34 AMPPART
2 hour hydrostatic test @ 200psi complete for overhead sprinkler piping. Rough to cover inspection complete for building 4, 1st level approved for cover, 2nd level needs tenting installed over piping in attic space, can not cover 2nd level until tenting is inspected.