BLD15-03423
| FIRE-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 3:10:33 PM | P | CANC |
|
|
Inspection request for life fire safety TCO will be rescheduled for 29JAN2018.
|
BLD15-03424
| FIRE-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 3:10:19 PM | P | CANC |
|
|
Inspection request for life fire safety TCO will be rescheduled for 29JAN2018.
|
BLD15-03835
| FIRE-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 3:10:06 PM | P | CANC |
|
|
Inspection request for life fire safety TCO will be rescheduled for 29JAN2018.
|
FIR16-00383
| INSP-Alarm Testing | 1/26/2018 | 1/26/2018 | 1/26/2018 3:09:11 PM | P | PART |
|
|
Fire alarm testing for levels 5 and 6 complete.
|
FIR17-00173
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 11:08:03 AM | A | PASS |
|
|
Final fire sprinkler inspection complete.
|
FIR17-00671
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 10:33:14 AM | A | FAIL |
|
|
Audible notification did not operate in area of work, visual notification operated correctly. Door holder magnet release was not tested, hardware was not installed on doors at time of inspection.
|
FIR17-00615
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 10:32:17 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
|
FIR17-00634
| INSP-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 10:31:59 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
|
BLD17-03709
| FIRE-Final Inspection | 1/26/2018 | 1/26/2018 | 1/26/2018 9:16:50 AM | A | FAIL |
|
|
Door holder magnets were not in place at time of inspection. Doors/door hardware were not installed on restroom doors at time of inspection. Fire alarms did not work correctly for final inspection which resulted in a failed inspection.
|
FIR17-00720
| INSP-Final Inspection | 1/26/2018 | 1/26/2018 | 1/26/2018 9:13:52 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
|
BLD12-01330
| FIRE-Final Inspection | 1/25/2018 | 1/26/2018 | 1/26/2018 8:20:57 AM | A | PASS |
|
|
Final life fire safety inspection complete.
|
FIR17-00448
| INSP-Sprinkler Rough-in | 1/25/2018 | 1/26/2018 | 1/26/2018 8:03:20 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
|