Inspections for the day of: Tuesday, January 27, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-02043 FIRE-Final Inspection1/27/20041/27/20041/27/2004 12:00:00 AMAPASS
fire life safety finaled 1/27/2004 9:12:10 AM
FIR03-00816 INSP-Sprinkler Rough-in/Hydro1/26/20041/27/20041/27/2004 12:00:00 AMAFAIL
Plans do not match the installed piping for layout or for pipe size. Sidewall head, on east side, in lobby needs to be extended coverage. Resubmitt plans 1/27/2004 10:11:15 AM
FIR03-00505 INSP-Final Inspection1/26/20041/27/20041/27/2004 12:00:00 AMPFAIL
provide knox box, provide map at the annunciator and label the zones at the annunciator 1/27/2004 1:52:28 PM
FIR03-00692 INSP-Sprinkler Rough-in/Hydro1/26/20041/27/20041/27/2004 12:00:00 AMPPART
Office areas are ok to cover 1/27/2004 1:49:28 PM
FIR03-00776 INSP-Final Inspection1/27/20041/27/20041/27/2004 12:00:00 AMPCANC
walt; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
FIR03-00816 INSP-Sprinkler Rough-in1/27/20041/27/20041/27/2004 12:00:00 AMPPART
Fire sprinkler piping in the office area is OK for cover per the resubmitted plans approved on 1/27/04 1/27/2004 3:19:15 PM
BLD02-02743 FIRE-Conference1/27/20041/27/20041/27/2004 12:00:00 AMPDONE
emergency lighting and exit signs as installed operated ok. No other items inspected
FIR03-00774 INSP-Final Inspection1/27/20041/27/20041/27/2004 12:00:00 AMPPASS
Fire sprinklers finaled
FIR04-00031 INSP-Final Inspection1/27/20041/27/20041/27/2004 12:00:00 AMPPART
A temporary occupancy until duct detectors have been tested
BLD03-02250 FIRE-Final Inspection1/27/20041/27/20041/27/2004 12:00:00 AMPPART
A temporary occupancy until duct detectors have been tested under the fire alarm permit. All other life safety items are OK