FIR04-00600
| FIR-Aging Inspection | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | | PART |
|
|
Talked to Laren and he will schedule for inspection 1/27/2005 9:11:30 AM
|
FIR04-00605
| INSP-Final Inspection | 1/26/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 1/26/2005 at 9:23:30 AM. Contact: ###-####. Rescheduled for 1/28 1/27/2005 9:03:12 AM
|
BLD04-02362
| FIRE-Final Inspection | 1/26/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | A | FAIL |
|
|
matt; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Need resubmittals to show duct detectors on zone 8; need to test duct detectors as units did not shut down 1/27/2005 10:35:52 AM
|
FIR04-00166
| INSP-Final Inspection | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | A | PART |
|
|
All items have been corrected from previous inspection 1/27/2005 8:30:39 AM
|
FIR03-00012
| INSP-Final Inspection | 1/26/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | A | NR |
|
|
linda; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Talked to Linda and the flow switch problem has been turned over to Viking 1/27/2005 8:15:50 AM
|
FIR04-00546
| INSP-Supply line flush | 1/26/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 1/26/2005 at 3:34:50 PM. Contact: ###-####. UG has been hydro'd and flushed 1/27/2005 8:16:38 AM
|
FIR04-00546
| INSP-Sprinkler Rough-in | 1/26/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | A | PART |
|
|
terrry - ###-#### Hydro failed; okay to cover areas identified on plans and resubmittals for beam areas 1/27/2005 10:45:23 AM
|
FIR04-00546
| INSP-Sprinkler Rough-in/Hydro | 1/26/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | A | PART |
|
|
###-#### - terry Note: please call prior to inspection Hydro failed; okay to cover areas identified on plans and resubmittals for beam areas 1/27/2005 10:45:36 AM
|
BLD04-02362
| FIRE-Conference | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | A | PART |
|
|
Met with GC while testing the alarms - need sprinkler head in riser room; room created for fire alarm panel requires heat; complete fire alarm permit 1/27/2005 10:37:33 AM
|
BLD04-01480
| FIRE-Final Inspection | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | A | PART |
|
|
Late AM if Posible; Phone #: ###-#### Internet Inspection Request from: David Mortensen All items corrected except the door hardware - put on temp occupancy per Sam R. pending final configuration of doors/hardware 1/27/2005 11:16:28 AM
|
FIR05-00034
| INSP-Final Inspection | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 1/27/2005 at 10:36:32 AM. Contact: ###-####.
|
BLD03-03048
| FIRE-Final Inspection | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | FAIL |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles The duct detectors are installed downstream of filters - need to be installed before filters; all other items have been corrected 1/27/2005 2:47:32 PM
|
BLD04-02182
| FIRE-Final Inspection | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
|
BLD03-01692
| FIRE-Final Inspection | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
|
FIR05-00019
| INSP-Final Inspection | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
final okay 1/27/2005 4:05:07 PM
|
FIR05-00042
| INSP-Final Inspection | 1/26/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
Contact: chris - Need at 1 PM - please call if not able to make this time.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
FIR05-00025
| INSP-Final Inspection | 1/26/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
burl; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
FIR05-00022
| INSP-Final Inspection | 1/26/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
burl; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
FIR05-00023
| INSP-Final Inspection | 1/26/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
burl; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
FIR04-00799
| INSP-Final Inspection | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
Please call Ryan Jenson @ ###-#### 1 Hour prior to arrival. Internet Inspection Request from: Trent Bice
|
FIR05-00028
| INSP-Final Inspection | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 1/27/2005 at 8:53:57 AM. Contact: ###-####.
|
BLD04-00450
| FIRE-Final Inspection | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 1/27/2005 at 9:05:48 AM. Contact: ###-####. Will need duct detectors on all RTU's per plans 1/27/2005 3:18:33 PM
|
BLD04-02366
| FIRE-Final Inspection | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
devine; Phone #: ###-#### Internet Inspection Request from: Barbara Moore The rack at the 2nd floor north exit will be removed 1/27/2005 1:44:22 PM
|
FIR04-00802
| INSP-Final Inspection | 1/26/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 1/26/2005 at 2:18:58 PM. Contact: ###-####.
|
MIS05-00011
| FIR-Final | 1/27/2005 | 1/27/2005 | 1/27/2005 12:00:00 AM | P | PASS |
|
|
dana-call 1st for access- re-insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|