Inspections for the day of: Thursday, January 27, 2005.
Number of inspections: 1
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00012 INSP-Final Inspection1/26/20051/27/20051/27/2005 12:00:00 AMAFAIL
Inspection was to verify that the waterflow switch is still intermittent as far as timing. It appears that the water for the sprinkler system is surging which won't allow the flow switch to activate. I left correction notice with Mountain Alarm and Eric with Red Cross 1/27/2005 8:17:47 AM