Inspections for the day of: Tuesday, January 27, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00901 FIR-Aging Inspection1/27/20091/27/20091/28/2009 5:46:51 PMPDONE
Confirm state elevator inspection.
FIR07-00928 INSP-Sprinkler Rough-in/Hydro1/26/20091/27/20091/27/2009 4:18:38 PMPPART
Fire pump acceptance testing including rated and 150% flow tests and rooftop flow test completed acceptable.
FIR08-00766 INSP-Sprinkler Rough-in1/27/20091/27/20091/27/2009 4:15:48 PMPPART
UG fire supply pipe per red-line annotations with todays date on approved plan set okayed for bury, (NE corner).
FIR08-00165 INSP-Final Inspection1/27/20091/27/20091/27/2009 3:33:40 PMPPASS
Fire sprinkler permit finaled.
FIR08-00165 FIR-Aging Inspection1/27/20091/27/20091/27/2009 3:33:11 PMPDONE
fpp permit open for first floor test kichen. 301 Okay for final. 410
FIR07-01005 FIR-Aging Inspection1/27/20091/27/20091/27/2009 3:30:02 PMPDONE
Fire sprinkler permit finaled.
FIR08-00461 INSP-Sprinkler Rough-in/Hydro1/23/20091/27/20091/27/2009 12:57:40 PMAPART
OH sprinkler piping and drops okayed for ceiling cover at the 7th floor common corridor, noted one missing hanger at an armover to be installed today, discussed sw head locations at the cable closets adjacent to the elevator hoistway.
BLD09-00045 FIRE-Final Inspection1/26/20091/27/20091/27/2009 12:54:30 PMAPASS
Life safety inspection passed.
FIR08-00641 INSP-Sprinkler Rough-in1/26/20091/27/20091/27/2009 12:04:01 PMAPART
OH fire sprinkler system modifications are okay for ceiling cover, noted some heads will need to be replaced due to paint/texture overspray-see annotations on plans.
FIR08-00724 FIR-Aging Inspection1/27/20091/27/20091/27/2009 11:26:47 AM DONE
WIP, pending site inspection request.