FIR09-00719
| INSP-Final Inspection | 1/27/2010 | 1/27/2010 | 1/27/2010 4:34:51 PM | P | CANC |
|
|
To be cancelled per Mike since there is no access to the fire alarm panel room.
|
FIR08-00754
| INSP-Final Inspection | 1/26/2010 | 1/27/2010 | 1/27/2010 3:39:01 PM | P | PASS |
|
|
Permit finaled.
|
BLD09-01781
| FIRE-Final Inspection | 1/26/2010 | 1/27/2010 | 1/27/2010 3:38:33 PM | A | FAIL |
|
|
The project related fire alarm permit needs to be finaled prior to a pass being given for this permit. Life safety is ok to sign off when fire alarm is complete.
|
FIR09-00729
| INSP-Final Inspection | 1/27/2010 | 1/27/2010 | 1/27/2010 12:59:38 PM | P | PASS |
|
|
Permit finaled. There was a NetCon rating of 5.
|
FIR09-00354
| INSP-Final Inspection | 1/27/2010 | 1/27/2010 | 1/27/2010 12:19:35 PM | P | FAIL |
|
|
When the battery in the AES panel was disconnected it reported as a supervisory on the FACP and did not report to the monitoring station. The FACP needs to be reprogrammed so that the AES trouble signals report to the FACP as trouble signals and then have the signals reverified at the monitoring station. Also the NetCon rating was only a 6. Tim stated that he would probably be installing a remote antenna.
|
BLD09-01780
| FIRE-Final Inspection | 1/26/2010 | 1/27/2010 | 1/27/2010 10:13:37 AM | A | PASS |
|
|
Life safety is passed. The fire alarm and fire sprinkler are non-applicable.
|
BLD09-01808
| FIRE-Final Inspection | 1/25/2010 | 1/27/2010 | 1/27/2010 9:31:19 AM | A | PASS |
|
|
Life safety passed
|