Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00719 INSP-Final Inspection1/27/20101/27/20101/27/2010 4:34:51 PMPCANC
To be cancelled per Mike since there is no access to the fire alarm panel room.
FIR08-00754 INSP-Final Inspection1/26/20101/27/20101/27/2010 3:39:01 PMPPASS
Permit finaled.
BLD09-01781 FIRE-Final Inspection1/26/20101/27/20101/27/2010 3:38:33 PMAFAIL
The project related fire alarm permit needs to be finaled prior to a pass being given for this permit. Life safety is ok to sign off when fire alarm is complete.
FIR09-00729 INSP-Final Inspection1/27/20101/27/20101/27/2010 12:59:38 PMPPASS
Permit finaled. There was a NetCon rating of 5.
FIR09-00354 INSP-Final Inspection1/27/20101/27/20101/27/2010 12:19:35 PMPFAIL
When the battery in the AES panel was disconnected it reported as a supervisory on the FACP and did not report to the monitoring station. The FACP needs to be reprogrammed so that the AES trouble signals report to the FACP as trouble signals and then have the signals reverified at the monitoring station. Also the NetCon rating was only a 6. Tim stated that he would probably be installing a remote antenna.
BLD09-01780 FIRE-Final Inspection1/26/20101/27/20101/27/2010 10:13:37 AMAPASS
Life safety is passed. The fire alarm and fire sprinkler are non-applicable.
BLD09-01808 FIRE-Final Inspection1/25/20101/27/20101/27/2010 9:31:19 AMAPASS
Life safety passed