Inspections for the day of: Thursday, January 27, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTim Frost
TitleFIRE PLANS EXAMINER
Phone #208-608-7110
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD10-00114 FIRE-Sprinkler Rough-in1/27/20111/27/20111/28/2011 12:00:00 AMPPART
This inspection was called in under the wrong permit. The permit should have been FIR10-00072.

The exterior canopy was inspected. The canopy is completely filled with non-combustible insulation. I gave then the ok to cover the canopy with hardy board.
FIR10-00540 INSP-Sprinkler Rough-in1/27/20111/27/20111/28/2011 12:00:00 AMPPART
Inspected the hanger attachment in the area on the second floor which will be covered with fire proofing. The attachments passed inspection.
FIR10-00072 INSP-Final Inspection1/27/20111/27/20111/27/2011 12:00:00 AMPPART
This inspection was called in under the wrong permit BLD10-00114.

The exterior canopy was inspected. The canopy is completely filled with non-combustible insulation. I gave then the ok to cover the canopy with hardy board. Therefore no sprinkler was required.
FIR10-00556 INSP-Final Inspection1/27/20111/27/20111/27/2011 12:00:00 AMPNR
Inspector unable to contact contractor to arrange for inspection. Inspector visited jobsite and no contractor was present. Inspection cancelled.
FIR11-00016 INSP-Sprinkler Rough-in/Hydro1/27/20111/27/20111/27/2011 12:00:00 AMPPASS
Hydro Passed.
Lower office area not previously inspected was ok to cover.