ELE10-02040
| ELE-Aging Inspection | 1/27/2012 | 1/27/2012 | 1/30/2012 10:24:11 AM | | DONE |
|
|
see final
|
ESC11-00719
| Aging Inspection | 1/27/2012 | 1/27/2012 | 1/30/2012 10:21:36 AM | | DONE |
|
|
looked ok
|
ELE10-00081
| Final | 1/27/2012 | 1/27/2012 | 1/27/2012 2:01:20 PM | P | CANC |
|
|
Contact: Spencer McLean Phone #: ###-#### >> Inspection requested via web by Deb Gooden called, electrician will set up inspection for equipment installation
|
ELE12-00166
| Rough-In Permanent Service | 1/27/2012 | 1/27/2012 | 1/27/2012 1:19:31 PM | P | PASS |
|
|
Re-inspect. Ryan is contact. Thank you Phone #: ###-#### >> Inspection requested via web by Chris Chesnut corrections made, ri ok, p/s u/g n ok
|
ELE11-02850
| Final | 1/27/2012 | 1/27/2012 | 1/27/2012 12:15:33 PM | P | PASS |
|
|
unit is open no tenants yet, push 5 or 6 on key pad for manager. He will let you in. Thanks Bob. Phone #: ###-#### >> Inspection requested via web by Julie Schroder ok final
|
ELE12-00166
| Rough-In Permanent Service | 1/26/2012 | 1/27/2012 | 1/27/2012 10:27:45 AM | A | FAIL |
|
|
Ryan is contact. Sorry about the back to back days. Have a good weekend and thanks. Phone #: ###-#### >> Inspection requested via web by Chris Chesnut called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 334.30 shall staple nm within 12" of panel, 250.86 shall ground metal boxes, 410.16(C) shall verify clothes closet fixtures provide clearance, BCC all make-up shall be done, shall provide boxes for nm cable, shall change room count on permit to 24 rooms
|
ELE12-00145
| Temporary Service | 1/25/2012 | 1/27/2012 | 1/27/2012 9:34:44 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE12-00146
| Rough-In Permanent Service | 1/25/2012 | 1/27/2012 | 1/27/2012 9:33:35 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk ri ok, p/s u/g n ok
|
ELE11-02242
| Final | 1/26/2012 | 1/27/2012 | 1/27/2012 8:14:45 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot ok final
|
ELE10-02067
| ELE-Aging Inspection | 1/27/2012 | 1/27/2012 | 1/27/2012 6:20:34 AM | | DONE |
|
|
waiting for contractor to prove unit listed, still under construction
|
ELE10-02055
| ELE-Aging Inspection | 1/27/2012 | 1/27/2012 | 1/27/2012 6:19:21 AM | | DONE |
|
|
no work done, see doc expire
|
ELE10-02055
| DOC - Permit Expired | 1/27/2012 | 1/27/2012 | 1/27/2012 6:19:09 AM | A | PASS |
|
|
other contractor did work, ok doc expire
|