Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02040 ELE-Aging Inspection1/27/20121/27/20121/30/2012 10:24:11 AM DONE
see final
ESC11-00719 Aging Inspection1/27/20121/27/20121/30/2012 10:21:36 AM DONE
looked ok
ELE10-00081 Final1/27/20121/27/20121/27/2012 2:01:20 PMPCANC
Contact: Spencer McLean Phone #: ###-#### >> Inspection requested via web by Deb Gooden called, electrician will set up inspection for equipment installation
ELE12-00166 Rough-In Permanent Service1/27/20121/27/20121/27/2012 1:19:31 PMPPASS
Re-inspect. Ryan is contact. Thank you Phone #: ###-#### >> Inspection requested via web by Chris Chesnut corrections made, ri ok, p/s u/g n ok
ELE11-02850 Final1/27/20121/27/20121/27/2012 12:15:33 PMPPASS
unit is open no tenants yet, push 5 or 6 on key pad for manager. He will let you in. Thanks Bob. Phone #: ###-#### >> Inspection requested via web by Julie Schroder ok final
ELE12-00166 Rough-In Permanent Service1/26/20121/27/20121/27/2012 10:27:45 AMAFAIL
Ryan is contact. Sorry about the back to back days. Have a good weekend and thanks. Phone #: ###-#### >> Inspection requested via web by Chris Chesnut called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 334.30 shall staple nm within 12" of panel, 250.86 shall ground metal boxes, 410.16(C) shall verify clothes closet fixtures provide clearance, BCC all make-up shall be done, shall provide boxes for nm cable, shall change room count on permit to 24 rooms
ELE12-00145 Temporary Service1/25/20121/27/20121/27/2012 9:34:44 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Alan Lusk t/s u/g n ok
ELE12-00146 Rough-In Permanent Service1/25/20121/27/20121/27/2012 9:33:35 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Alan Lusk ri ok, p/s u/g n ok
ELE11-02242 Final1/26/20121/27/20121/27/2012 8:14:45 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot ok final
ELE10-02067 ELE-Aging Inspection1/27/20121/27/20121/27/2012 6:20:34 AM DONE
waiting for contractor to prove unit listed, still under construction
ELE10-02055 ELE-Aging Inspection1/27/20121/27/20121/27/2012 6:19:21 AM DONE
no work done, see doc expire
ELE10-02055 DOC - Permit Expired1/27/20121/27/20121/27/2012 6:19:09 AMAPASS
other contractor did work, ok doc expire