FIR07-00757
| FIR-Aging Inspection | 1/27/2014 | 1/27/2014 | 1/28/2014 9:08:31 AM | | NR |
|
|
Company is out of business
|
FIR14-00011
| INSP-Final Inspection | 1/24/2014 | 1/27/2014 | 1/27/2014 3:43:05 PM | P | CANC |
|
|
Pat-Cooking Hood Phone #: ###-####
|
BLD13-02937
| FIRE-Final Inspection | 1/24/2014 | 1/27/2014 | 1/27/2014 3:16:14 PM | P | PASS |
|
|
life safety passed
|
BLD14-00085
| FIRE-Final Inspection | 1/27/2014 | 1/27/2014 | 1/27/2014 2:42:56 PM | P | PASS |
|
|
life safety passed
|
FIR13-00522
| INSP-Sprinkler Rough-in | 1/27/2014 | 1/27/2014 | 1/27/2014 2:27:04 PM | P | PASS |
|
|
Not ready for an underground flush but the above ground rough-in inspection passed except the pendant head in the gas fire place still needs installed and the batt insulation installed on the branchline risers prior to a cover approval on the piping.
|
BLD13-02639
| FIRE-Final Inspection | 1/27/2014 | 1/27/2014 | 1/27/2014 2:25:19 PM | P | FAIL |
|
|
Provide duct smoke detector and remoter annunciator in hvac unit 5 as per the plans (and test), hvac unit 6 shows a duct smoke detector as well and if installed will need an annunciator and tested too. Also need panic hardware on the two north exits as per the door schedule, need to repair the two exit discharge lights at the north exits and mount the four fire extinguishers as discussed.
|
FIR13-00666
| INSP-Final Inspection | 1/27/2014 | 1/27/2014 | 1/27/2014 1:53:08 PM | P | PASS |
|
|
Permit finaled
|
BLD13-03298
| FIRE-Final Inspection | 1/27/2014 | 1/27/2014 | 1/27/2014 10:51:36 AM | A | FAIL |
|
|
See the city approved plans for corrections and their locations which include door hardware, fire extinguisher on mezzanine level and signage at the main exit door and the gas storage rooms.
|
BLD13-03236
| FIRE-Final Inspection | 1/23/2014 | 1/27/2014 | 1/27/2014 10:43:02 AM | A | PASS |
|
|
life safety passed. no racking or storage of product was present at the time of inspection.
|
FIR13-00685
| INSP-Final Inspection | 1/23/2014 | 1/27/2014 | 1/27/2014 9:29:32 AM | A | PASS |
|
|
Permit finaled
|
BLD13-03087
| FIRE-Conference | 1/24/2014 | 1/27/2014 | 1/27/2014 9:24:10 AM | A | DONE |
|
|
Provide approved hardware at both the front exit and rear exits and provide current inspection for the fire extinguishers.
|
BLD13-02639
| FIRE-Final Inspection | 1/24/2014 | 1/27/2014 | 1/27/2014 8:23:52 AM | A | FAIL |
|
|
Contractor was not on site and I could not locate any city approved drawings.
|