Inspections for the day of: Monday, January 27, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00757 FIR-Aging Inspection1/27/20141/27/20141/28/2014 9:08:31 AM NR
Company is out of business
FIR14-00011 INSP-Final Inspection1/24/20141/27/20141/27/2014 3:43:05 PMPCANC
Pat-Cooking Hood Phone #: ###-####
BLD13-02937 FIRE-Final Inspection1/24/20141/27/20141/27/2014 3:16:14 PMPPASS
life safety passed
BLD14-00085 FIRE-Final Inspection1/27/20141/27/20141/27/2014 2:42:56 PMPPASS
life safety passed
FIR13-00522 INSP-Sprinkler Rough-in1/27/20141/27/20141/27/2014 2:27:04 PMPPASS
Not ready for an underground flush but the above ground rough-in inspection passed except the pendant head in the gas fire place still needs installed and the batt insulation installed on the branchline risers prior to a cover approval on the piping.
BLD13-02639 FIRE-Final Inspection1/27/20141/27/20141/27/2014 2:25:19 PMPFAIL
Provide duct smoke detector and remoter annunciator in hvac unit 5 as per the plans (and test), hvac unit 6 shows a duct smoke detector as well and if installed will need an annunciator and tested too. Also need panic hardware on the two north exits as per the door schedule, need to repair the two exit discharge lights at the north exits and mount the four fire extinguishers as discussed.
FIR13-00666 INSP-Final Inspection1/27/20141/27/20141/27/2014 1:53:08 PMPPASS
Permit finaled
BLD13-03298 FIRE-Final Inspection1/27/20141/27/20141/27/2014 10:51:36 AMAFAIL
See the city approved plans for corrections and their locations which include door hardware, fire extinguisher on mezzanine level and signage at the main exit door and the gas storage rooms.
BLD13-03236 FIRE-Final Inspection1/23/20141/27/20141/27/2014 10:43:02 AMAPASS
life safety passed. no racking or storage of product was present at the time of inspection.
FIR13-00685 INSP-Final Inspection1/23/20141/27/20141/27/2014 9:29:32 AMAPASS
Permit finaled
BLD13-03087 FIRE-Conference1/24/20141/27/20141/27/2014 9:24:10 AMADONE
Provide approved hardware at both the front exit and rear exits and provide current inspection for the fire extinguishers.
BLD13-02639 FIRE-Final Inspection1/24/20141/27/20141/27/2014 8:23:52 AMAFAIL
Contractor was not on site and I could not locate any city approved drawings.