Inspections for the day of: Tuesday, January 27, 2015.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00659 INSP-Final Inspection1/26/20151/27/20151/28/2015 3:18:21 PMAPASS
Scope of work completed, final walkthrough finished. Hydrostatic test passed.
NAF15-00001 INSP-Sprinkler Rough-in/Hydro1/26/20151/27/20151/27/2015 3:23:46 PMAPART
UG fire supply line hydrostatic test completed.
FIR14-00726 INSP-Final Inspection1/27/20151/27/20151/27/2015 3:22:41 PMAPART
Notification appliances per the scope of work tested satisfactory.
FIR14-00531 INSP-Sprinkler Rough-in1/26/20151/27/20151/27/2015 1:28:21 PMAPART
Center pendent head and branch at the pods tower one podium level thru 4th floor okay for sheetrock ceiling cover.
FIR14-00781 INSP-Final Inspection1/22/20151/27/20151/27/2015 10:37:44 AMAFAIL
Manual pull stations need relocated as indicated per the project scope and plan review comment #19, provide knox box per review note #9.
BLD14-03137 FIRE-Final Inspection1/26/20151/27/20151/27/2015 9:50:17 AMAPASS
Life safety inspection completed satisfactory. No signature card available on site.