Inspections for the day of: Wednesday, January 27, 2016.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02038 ELE-Aging Inspection1/27/20161/27/20162/4/2016 4:15:05 PM PASS
Waiting for contactor to schedule
ELE15-04094 Final1/26/20161/27/20161/27/2016 2:40:11 PMPFAIL
Electrical Final - Kitchen Remodel Tim ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence
Kitchen checked out ok.
4-05-32- code violation not to be retained.
300.15- A box shall be installed at each splice. Basement.
314.25- Each box shall have a cover. Basement
ELE16-00253 Electrical Rough-In1/27/20161/27/20161/27/2016 2:11:26 PMPPASS
Scott. Wall cover for (3) new outlets in half wall. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Area listed wall rough in ok cover
ELE15-03813 Final1/27/20161/27/20161/27/2016 1:41:44 PMPPASS
Garage code is 0500 Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
ELE16-00008 Rough-In Permanent Service1/27/20161/27/20161/27/2016 12:47:04 PMPPASS
Mike Phone #: ###-#### Service only at this time. p/s u/g n ok
MIS16-00015 ELE-Conference1/20/20161/27/20161/27/2016 12:17:21 PMADONE
Check back on hot tub installed with out permit. Owner called and stated they will hire a contractor and they are pulling permit 1-27-16. As of noon not shown
ELE15-03960 Final1/26/20161/27/20161/27/2016 10:25:25 AMAFAIL
Garage door will be open for inspection. Phone #: ###-#### Inspection requested via web by Barbara Szurgot
410.30- Luminaires shall be securely supported. 2 fixtures hanging on supply cord.
410.62(C)(2)(b)- Flexible cords shall not be under strain.
314.25- All boxes shall have covers. HVAC not complete. out back and ceiling in existing portion of garage.
ELE15-02429 Final1/26/20161/27/20161/27/2016 9:45:00 AMAPASS
Swimming pool electrical. Equipment room is unlocked and accessible. Phone #: ###-#### Inspection requested via web by Lars Johnson Final ok
ELE15-04003 Final1/26/20161/27/20161/27/2016 9:00:36 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson Final ok