ELE05-00291
| Permanent Service | 1/27/2005 | 1/28/2005 | 1/28/2005 12:00:00 AM | A | CANC |
|
|
###-#### see added final no p/s 1/28/2005 9:21:56 AM
|
ELE04-02543
| Final | 1/27/2005 | 1/28/2005 | 1/28/2005 12:00:00 AM | A | FAIL |
|
|
please call prior to inspection so he can meet ya there//brett; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called 210.8 gfci for unfinished basement recepts, 310.15 derate wires in pvc at p/s, also all pvc fittings shall be made up tightand LB covers and gaskets, 250.52(A)(1) terminate GEC from water to p/s, 620.52 install labels noting 2 power sources,and warning signs, 250.24(A)(5) isolate all neutrals and grds at all sub gear check elevator disconnect also,, note elevator contractor needs permit, is he licensed in Idaho?, all elevator wiring shall meet NEC required outlets for equip rm connectors for flex, cables, and low voltage shall have proper voltage rating when install with high voltage in cabinet 1/28/2005 1:17:59 PM
|
ELE05-00294
| Rough-In Permanent Service | 1/27/2005 | 1/28/2005 | 1/28/2005 12:00:00 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS cor. posted needs dinning rm on kit circuit, needs countertop outlets, outlet 2ft wall sw bedrm, 300.4 for low voltage called see added p/s 1/28/2005 10:55:42 AM
|
ELE05-00291
| Final | 1/28/2005 | 1/28/2005 | 1/28/2005 12:00:00 AM | A | PASS |
|
|
ok
|
ELE05-00294
| Permanent Service | 1/28/2005 | 1/28/2005 | 1/28/2005 12:00:00 AM | A | PASS |
|
|
p/s u/g new ok
|
ELE04-03982
| Final | 1/28/2005 | 1/28/2005 | 1/28/2005 12:00:00 AM | P | FAIL |
|
|
kim ; Phone #: ###-#### Internet Inspection
Request from: Marsha Smylie cor. posted called, 300.10 bond bushing for REwashers, 314.28, shall provide required distance between raceways, as code noted states, 250.148 tag equip grd to boxes, power for press red taged and turned off,
asked owner frist if press power could be turned off he said yes ETL testing did not follow Boise City process for field testing
1/28/2005 5:00:41 PM 1/28/2005 5:01:11 PM
|
ELE05-00068
| Permanent Service | 1/28/2005 | 1/28/2005 | 1/28/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 1/28/2005 at 11:09:06 AM. Contact: ###-####. corrections not made same cor. posted called also reinspection fee due posted 1/28/2005 4:02:37 PM
|
ELE04-02648
| Final | 1/28/2005 | 1/28/2005 | 1/28/2005 12:00:00 AM | P | FAIL |
|
|
Would like inspection asap. Thanks.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs cor. posted called 210.52(C) required outlet spacing counter in din rm, box fill and protect romex island counter, 210.12 arc-fault for bath circuit in bedrms,seal KOs in back of fixtures,a dn use connectors for cables and leave open so I can inspect, is outside ceiling fan approved for outside 1/28/2005 2:15:22 PM
|