ELE07-04220
| Final | 1/28/2008 | 1/28/2008 | 1/28/2008 4:29:33 PM | P | PASS |
|
|
Final Inspection In Store Pizzeria Albertson 189 36th & State Rick ###-#### Phone #: ###-#### Internet Inspection Request from: Kelly Felin ok no card
|
ELE08-00212
| Temporary Service | 1/28/2008 | 1/28/2008 | 1/28/2008 3:49:56 PM | P | FAIL |
|
|
kevin Phone #: ###-#### corr. called use plastic or listed conn. for GEC, 250.24&28 install bonding jumper from equip grd bus to neutral bus
|
ELE07-03838
| Rough-In Permanent Service | 1/28/2008 | 1/28/2008 | 1/28/2008 3:01:37 PM | P | CANC |
|
|
darlene Phone #: ###-#### see r/i request, p/s not ready
|
ELE07-03838
| Electrical Rough-In | 1/28/2008 | 1/28/2008 | 1/28/2008 2:58:13 PM | P | PASS |
|
|
darlene Phone #: ###-#### r/i ok all walls and hard ceilings
|
ELE07-03907
| Electrical Rough-In | 1/28/2008 | 1/28/2008 | 1/28/2008 1:39:01 PM | P | PART |
|
|
Contact is Brian Cornell. St. Mark''s School Addition. We would like to be onsite at time of inspection. Please call us, maybe 30-60 minutes before your arrival and we will head to the site. Brian=###-#### or Jay ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery r/i walls and hard ceilings new class rooms
|
ELE07-03907
| Conference | 1/28/2008 | 1/28/2008 | 1/28/2008 1:38:14 PM | P | DONE |
|
|
Contact is Brian Cornell. St. Mark''s School Addition. We would like to be onsite at time of inspection. Please call us, maybe 30-60 minutes before your arrival and we will head to the site. Brian=###-#### or Jay ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery conference on new p/s refeeding old p/s that will become sub gear, and outside feeder and grding to seperate building
|
ELE07-03632
| Final | 1/28/2008 | 1/28/2008 | 1/28/2008 11:07:26 AM | A | PASS |
|
|
ok
|
ELE06-04473
| ELE-Aging Inspection | 1/28/2008 | 1/28/2008 | 1/28/2008 10:11:01 AM | | DONE |
|
|
|
ELE06-04473
| DOC - Permit Expired | 1/28/2008 | 1/28/2008 | 1/28/2008 10:10:49 AM | A | PASS |
|
|
contr will not respond back
|
ELE07-03998
| Electrical Rough-In | 1/25/2008 | 1/28/2008 | 1/28/2008 9:46:57 AM | A | PASS |
|
|
zymber Phone #: ###-#### ok
|
ELE08-00163
| Temporary Service | 1/25/2008 | 1/28/2008 | 1/28/2008 8:46:27 AM | A | PASS |
|
|
Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek t/s u/g new ok
|