BLD07-02896
| FIRE-Final Inspection | 1/28/2008 | 1/28/2008 | 1/28/2008 4:31:39 PM | P | FAIL |
|
|
A waist high conveyor system is blocking the exit/fire dept access doors on the east wall. Also the fire extinguishers along this wall are now inaccessible. Other fire extinguishers in the middle of the building are buried in product and need relocated to where they will be accessible.
|
FIR07-01050
| INSP-Sprinkler Rough-in | 1/24/2008 | 1/28/2008 | 1/28/2008 4:29:03 PM | A | FAIL |
|
|
The piping installation is acceptable but the second floor pipe size does not match plans. I spoke to John Edes and let him know that the pipe size will need to be approved by Brian Johnson prior to cover permission being given. No piping can be covered at this point.
|
FIR07-00579
| INSP-Sprinkler Rough-in | 1/25/2008 | 1/28/2008 | 1/28/2008 4:27:03 PM | A | PASS |
|
|
The remaining piping to be inspected is the girls and boys restrooms and cafeteria. The sprinkler drops have not been installed yet either.
|
FIR07-01046
| INSP-Sprinkler Rough-in | 1/25/2008 | 1/28/2008 | 1/28/2008 1:25:58 PM | A | PASS |
|
|
The sprinkler piping is ok to cover.
|
FIR08-00063
| INSP-Final Inspection | 1/25/2008 | 1/28/2008 | 1/28/2008 10:26:02 AM | A | PASS |
|
|
Hood suppression system operated correctly.
|