Inspections for the day of: Thursday, January 28, 2010.
Number of inspections: 14
Percentage of inspections complete: 93 %
Percentage of inspections not complete: 7 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00675 INSP-Final Inspection1/22/20101/25/2010 A 
trent Phone #: ###-####
FIR09-00612 INSP-Supply line flush1/27/20101/28/20102/1/2010 4:24:28 PMPPART
Supply line flush okayed per site visit and activity notes 1/29.
FIR09-00409 INSP-Final Inspection1/27/20101/28/20101/28/2010 4:56:28 PMPFAIL
On site netcon reported a "6" at the time of inspection.
FIR09-00411 INSP-Final Inspection1/27/20101/28/20101/28/2010 4:55:07 PMPPASS
Fire alarm permit work passed inspection after corrections made while on site to amend account information to include correct zones and descriptors for signals transmitted including trouble and supervisory conditions.
FIR09-00410 INSP-Final Inspection1/27/20101/28/20101/28/2010 4:54:41 PMPPASS
Fire alarm permit work passed inspection after corrections made while on site to amend account information to include correct zones and descriptors for signals transmitted including trouble and supervisory conditions.
FIR10-00019 INSP-Sprinkler Rough-in/Hydro1/28/20101/28/20101/28/2010 4:50:34 PMPPART
Circled and initialed plans with today's date for area approved for ceiling cover at the TI.
FIR09-00702 INSP-Final Inspection1/28/20101/28/20101/28/2010 4:49:27 PMPPASS
Okayed for final when two missing escutcheons are installed- to be done today per GC.
BLD09-00378 FIRE-Final Inspection1/27/20101/28/20101/28/2010 4:48:01 PMPDEFR
Pending project related fire alarm permit final.
FIR09-00347 INSP-Final Inspection1/26/20101/28/20101/28/2010 1:08:09 PMANR
Pending project related fire alarm permit finals.
BLD09-01705 FIRE-Final Inspection1/27/20101/28/20101/28/2010 1:07:02 PMAPASS
Scope of work completed acceptable, fire life safety final passed.
BLD10-00025 FIRE-Final Inspection1/27/20101/28/20101/28/2010 1:05:46 PMAPASS
Fire life safety inspection passed.
FIR09-00740 INSP-Final Inspection1/27/20101/28/20101/28/2010 1:05:02 PMANR
Pending plan resubmittals and project final for site related permit # FIR09-00608.
BLD09-02263 FIRE-Final Inspection1/27/20101/28/20101/28/2010 1:00:22 PMAFAIL
Noted overspaced fire sprinkler heads due to the scope of remodel work. New wall has created deficiencies at the public works office area.
FIR09-00652 INSP-Final Inspection1/27/20101/28/20101/28/2010 12:56:30 PMANR
Craig Phone #: ###-#### *Re-scheduled per phone call from contractor for 1/29/10.