Inspections for the day of: Friday, January 28, 2011.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00144 Electrical Rough-In1/28/20111/28/20111/28/2011 3:08:56 PMPPASS
John Phone #: ###-#### u/g towards transformer ok
ELE11-00169 Permanent Service1/28/20111/28/20111/28/2011 2:45:25 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson wrong type request, saw ipco u/g instead, looked ok to cover
ELE11-00168 Conference1/28/20111/28/20111/28/2011 2:44:11 PMPDONE
Please call to meet. Phone #: ###-#### >> Inspection requested via web by David Oliver talked about remodel for room and j-boxes
ELE11-00152 Electrical Rough-In1/28/20111/28/20111/28/2011 2:39:14 PMPNH
derrick Phone #: ###-#### called, left card, explained inspection process, told to call when access available
ELE11-00138 Electrical Rough-In1/28/20111/28/20111/28/2011 1:59:15 PMPPASS
Installed two new 20A circuits. 1 - 1P Exterior signs, 1 - 2P Vehicle lift, & added new outlets in the front waiting room. Phone #: ###-#### >> Inspection requested via web by nathan palmer ri ok
ELE11-00138 Final1/28/20111/28/20111/28/2011 1:20:14 PMPPASS
Installed two new 20A circuits. 1 - 1P Exterior signs, 1 - 2P Vehicle lift, & added new outlets in the front waiting room. Phone #: ###-#### >> Inspection requested via web by nathan palmer ok final
ELE11-00103 Electrical Rough-In1/28/20111/28/20111/28/2011 12:25:44 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by fred lopez met contractor, NEC 330.30(B) shall secure mc cable within 12" of termination, using cut in emergency fixtures, check license for Fred, his was expired, told to call for am inspections
ESC10-00638 General Inspection1/28/20111/28/20111/28/2011 10:14:43 AMAPASS
looked ok
ELE11-00164 Rough-In Permanent Service1/27/20111/28/20111/28/2011 10:09:22 AMAFAIL
late am please//Lucas ###-#### called, talked with owner for correction notice, referred to BCC 4-05-32 no violations shall be retained, ground rods shall be minimum 6' apart, there shall be no foreign piping below panel, shall not use metal romex connector for grounding electrode conductor, shall strap riser within 3' of service, need to see sub-panel and verify water pipe ground
ESC10-00796 General Inspection1/28/20111/28/20111/28/2011 9:16:32 AMAPASS
looked ok
ELE10-02538 Final1/27/20111/28/20111/28/2011 8:20:28 AMAPART
Phone #: ###-#### >> Inspection requested via web by Dan Hardisty only west 1/2 done, rest not ready, need to check all furniture, receptacle plates off for painting
ELE11-00144 Electrical Rough-In1/27/20111/28/20111/27/2011 2:56:25 PMAPASS
John Phone #: ###-#### ok cover electrodes