ELE11-00144
| Electrical Rough-In | 1/28/2011 | 1/28/2011 | 1/28/2011 3:08:56 PM | P | PASS |
|
|
John Phone #: ###-#### u/g towards transformer ok
|
ELE11-00169
| Permanent Service | 1/28/2011 | 1/28/2011 | 1/28/2011 2:45:25 PM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson wrong type request, saw ipco u/g instead, looked ok to cover
|
ELE11-00168
| Conference | 1/28/2011 | 1/28/2011 | 1/28/2011 2:44:11 PM | P | DONE |
|
|
Please call to meet. Phone #: ###-#### >> Inspection requested via web by David Oliver talked about remodel for room and j-boxes
|
ELE11-00152
| Electrical Rough-In | 1/28/2011 | 1/28/2011 | 1/28/2011 2:39:14 PM | P | NH |
|
|
derrick Phone #: ###-#### called, left card, explained inspection process, told to call when access available
|
ELE11-00138
| Electrical Rough-In | 1/28/2011 | 1/28/2011 | 1/28/2011 1:59:15 PM | P | PASS |
|
|
Installed two new 20A circuits. 1 - 1P Exterior signs, 1 - 2P Vehicle lift, & added new outlets in the front waiting room. Phone #: ###-#### >> Inspection requested via web by nathan palmer ri ok
|
ELE11-00138
| Final | 1/28/2011 | 1/28/2011 | 1/28/2011 1:20:14 PM | P | PASS |
|
|
Installed two new 20A circuits. 1 - 1P Exterior signs, 1 - 2P Vehicle lift, & added new outlets in the front waiting room. Phone #: ###-#### >> Inspection requested via web by nathan palmer ok final
|
ELE11-00103
| Electrical Rough-In | 1/28/2011 | 1/28/2011 | 1/28/2011 12:25:44 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by fred lopez met contractor, NEC 330.30(B) shall secure mc cable within 12" of termination, using cut in emergency fixtures, check license for Fred, his was expired, told to call for am inspections
|
ESC10-00638
| General Inspection | 1/28/2011 | 1/28/2011 | 1/28/2011 10:14:43 AM | A | PASS |
|
|
looked ok
|
ELE11-00164
| Rough-In Permanent Service | 1/27/2011 | 1/28/2011 | 1/28/2011 10:09:22 AM | A | FAIL |
|
|
late am please//Lucas ###-#### called, talked with owner for correction notice, referred to BCC 4-05-32 no violations shall be retained, ground rods shall be minimum 6' apart, there shall be no foreign piping below panel, shall not use metal romex connector for grounding electrode conductor, shall strap riser within 3' of service, need to see sub-panel and verify water pipe ground
|
ESC10-00796
| General Inspection | 1/28/2011 | 1/28/2011 | 1/28/2011 9:16:32 AM | A | PASS |
|
|
looked ok
|
ELE10-02538
| Final | 1/27/2011 | 1/28/2011 | 1/28/2011 8:20:28 AM | A | PART |
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Hardisty only west 1/2 done, rest not ready, need to check all furniture, receptacle plates off for painting
|
ELE11-00144
| Electrical Rough-In | 1/27/2011 | 1/28/2011 | 1/27/2011 2:56:25 PM | A | PASS |
|
|
John Phone #: ###-#### ok cover electrodes
|