Inspections for the day of: Monday, January 28, 2013.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00172 Rough-In Permanent Service1/28/20131/28/20131/28/2013 2:33:23 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson Service grounding electrode conductor not installed
ELE13-00172 Electrical Rough-In1/28/20131/28/20131/28/2013 2:27:41 PMPPASS
rough-in ok cover
ELE12-01364 Final1/28/20131/28/20131/28/2013 1:56:06 PMPPASS
Roger Phone #: ###-#### final ok
ELE12-02725 Final1/28/20131/28/20131/28/2013 1:17:29 PMPFAIL
TANKS. BILL Phone #: ###-#### >> Inspection requested via web by Bob Glenn NEC 210.8(A) All 15 and 20 ampere 120 volt receptacle in kitchen area (including pantry) require GFCI protection. Main breaker in panel requires label as main breaker. Boise city energy code requires at least 50% CFL's inside lighting fixtures
ELE13-00156 Rough-In Permanent Service1/28/20131/28/20131/28/2013 12:50:00 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson rough-in p/s u/g n ok
GCE12-00173 GCE-Final1/28/20131/28/20131/28/2013 12:14:26 PMPPASS
Daniel @ ###-#### final ok
GCE12-00177 GCE-Final1/28/20131/28/20131/28/2013 12:07:06 PMPPASS
Daniel @ ###-#### final ok
ELE13-00036 Final1/27/20131/28/20131/28/2013 9:49:21 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Stan Woodward final ok
ELE13-00163 Final1/25/20131/28/20131/28/2013 9:32:30 AMAFAIL
lock box code 4923 IPCo requested re-connect Phone #: ###-#### >> Inspection requested via web by Robert Jangula NEC 250.56 Second ground needed,six feet apart from first ground rod. Bonding jumper between hot and cold piping
ELE13-00117 Permanent Service1/25/20131/28/20131/28/2013 9:10:40 AMAFAIL
Contact: Justin Hugo Phone #: ###-#### >> Inspection requested via web by Deb Gooden main breaker shall have sufficient AFCI rating . Need fault current rating from Idaho Power for that location
ELE13-00165 Rough-In Permanent Service1/25/20131/28/20131/28/2013 8:16:16 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Joe Thomas rough-in p/s u/g n ok
ELE13-00141 Rough-In Permanent Service1/25/20131/28/20131/28/2013 8:15:26 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Joe Thomas rough-in p/s u/g n ok