Inspections for the day of: Wednesday, January 28, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-02129 ELE-Aging Inspection1/28/20151/28/20152/2/2015 4:50:02 PM DONE
too busy
ELE15-00218 Electrical Rough-In1/28/20151/28/20151/28/2015 4:34:59 PMPPASS
Phone #: ###-#### Inspection requested via web by ron spen cer garage r/i ok to cover
ELE15-00216 Rough-In Permanent Service1/28/20151/28/20151/28/2015 4:04:59 PMPPASS
Ok for Idaho power to re-connect Phone #: ###-#### Inspection requested via web by Randy Fletcher p/s o/h rec ok r/i not needed..NOTE:old deck and hot tub will need to be removed prior to final insp. If we don't here back within 10days, Idaho Power will be asked to remove meter
ELE15-00162 Rough-In Permanent Service1/28/20151/28/20151/28/2015 3:23:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn r/i ok p/s u/g n ok
ELE14-03191 Final1/28/20151/28/20151/28/2015 2:59:15 PMPPASS
GARAGE CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn final ok
ELE15-00124 Electrical Rough-In1/28/20151/28/20151/28/2015 1:59:21 PMPPASS
Jose Phone #: ###-#### 15th floor r/i walls ok confirm ground wire is solid under ground screw in each 4 sq. box upon return
ELE15-00211 Permanent Service1/27/20151/28/20151/28/2015 11:45:10 AMACANC
If you could call me first be for you come that would be great. Phone #: ###-#### Inspection requested via web by Neal Rumsey needed conference
ELE15-00211 Conference1/28/20151/28/20151/28/2015 11:44:39 AMPDONE
If you could call me first be for you come that would be great. Phone #: ###-#### Inspection requested via web by Neal Rumsey conference to look at Id. Power direct burial feed can be set in j-box and rerouted to new meter base. Neal says Id. power ok with it.
ELE15-00004 Electrical Rough-In1/27/20151/28/20151/28/2015 11:00:58 AMAFAIL
Call for access - Jose Phone #: ###-#### 300.4(A)(1)--bored holes in wood members shall be minimum 11/4" to edge of member. 334.30- secure NM cable within 12" of box. (conductors outside of box in liv.rm recept.
ELE15-00004 Permanent Service1/28/20151/28/20151/28/2015 10:58:31 AMPPASS
Call for access - Jose Phone #: ###-#### p/s o/h rec ok
GCE14-00212 GCE-Final1/27/20151/28/20151/28/2015 10:08:31 AMAFAIL
Penny ###-#### 406.5(C)-receptacles mounted to covers shall have more than on screw, 210.4(B)-where a multiwire branch circuit feeds one device both circuits shall be disconnected simultaneuosly. 348.30-flexable metal conduit shall be secured within 12inches of cabinet. (Also locknut is loose). 358.30-EMT shall be secured within 3 foot of cabinet. 300.4(G)-#4 conductors and larger shall be protected by an insulated fitting or plastic bushing. 408.7-unused openings shall be closedwith KO seals.
ELE15-00208 Temporary Service1/27/20151/28/20151/28/2015 8:56:53 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok