ELE09-02129
| ELE-Aging Inspection | 1/28/2015 | 1/28/2015 | 2/2/2015 4:50:02 PM | | DONE |
|
|
too busy
|
ELE15-00218
| Electrical Rough-In | 1/28/2015 | 1/28/2015 | 1/28/2015 4:34:59 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer garage r/i ok to cover
|
ELE15-00216
| Rough-In Permanent Service | 1/28/2015 | 1/28/2015 | 1/28/2015 4:04:59 PM | P | PASS |
|
|
Ok for Idaho power to re-connect Phone #: ###-#### Inspection requested via web by Randy Fletcher p/s o/h rec ok r/i not needed..NOTE:old deck and hot tub will need to be removed prior to final insp. If we don't here back within 10days, Idaho Power will be asked to remove meter
|
ELE15-00162
| Rough-In Permanent Service | 1/28/2015 | 1/28/2015 | 1/28/2015 3:23:01 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn r/i ok p/s u/g n ok
|
ELE14-03191
| Final | 1/28/2015 | 1/28/2015 | 1/28/2015 2:59:15 PM | P | PASS |
|
|
GARAGE CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn final ok
|
ELE15-00124
| Electrical Rough-In | 1/28/2015 | 1/28/2015 | 1/28/2015 1:59:21 PM | P | PASS |
|
|
Jose Phone #: ###-#### 15th floor r/i walls ok confirm ground wire is solid under ground screw in each 4 sq. box upon return
|
ELE15-00211
| Permanent Service | 1/27/2015 | 1/28/2015 | 1/28/2015 11:45:10 AM | A | CANC |
|
|
If you could call me first be for you come that would be great. Phone #: ###-#### Inspection requested via web by Neal Rumsey needed conference
|
ELE15-00211
| Conference | 1/28/2015 | 1/28/2015 | 1/28/2015 11:44:39 AM | P | DONE |
|
|
If you could call me first be for you come that would be great. Phone #: ###-#### Inspection requested via web by Neal Rumsey conference to look at Id. Power direct burial feed can be set in j-box and rerouted to new meter base. Neal says Id. power ok with it.
|
ELE15-00004
| Electrical Rough-In | 1/27/2015 | 1/28/2015 | 1/28/2015 11:00:58 AM | A | FAIL |
|
|
Call for access - Jose Phone #: ###-#### 300.4(A)(1)--bored holes in wood members shall be minimum 11/4" to edge of member. 334.30- secure NM cable within 12" of box. (conductors outside of box in liv.rm recept.
|
ELE15-00004
| Permanent Service | 1/28/2015 | 1/28/2015 | 1/28/2015 10:58:31 AM | P | PASS |
|
|
Call for access - Jose Phone #: ###-#### p/s o/h rec ok
|
GCE14-00212
| GCE-Final | 1/27/2015 | 1/28/2015 | 1/28/2015 10:08:31 AM | A | FAIL |
|
|
Penny ###-#### 406.5(C)-receptacles mounted to covers shall have more than on screw, 210.4(B)-where a multiwire branch circuit feeds one device both circuits shall be disconnected simultaneuosly. 348.30-flexable metal conduit shall be secured within 12inches of cabinet. (Also locknut is loose). 358.30-EMT shall be secured within 3 foot of cabinet. 300.4(G)-#4 conductors and larger shall be protected by an insulated fitting or plastic bushing. 408.7-unused openings shall be closedwith KO seals.
|
ELE15-00208
| Temporary Service | 1/27/2015 | 1/28/2015 | 1/28/2015 8:56:53 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|