Inspections for the day of: Wednesday, January 29, 1997.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE97-00170 INSP - Electrical Rough-In1/28/19971/29/19971/29/1997 12:00:00 AMACANC
01/29/97 315 - REINSPECTION was done 01/28/97 see other inspection reque
ELE97-00242 INSP - Ele Rough-In/Perm Svc1/28/19971/29/19971/29/1997 12:00:00 AMAFAIL
01/29/97 315 - no access for 09 notice and cor. posted NEC,250-24 table shall be #2 250-91 no splices allowed in GEC, BCC shall install concrete encased electrode
ELE97-00245 INSP - Ele Rough-In/Perm Svc1/29/19971/29/19971/29/1997 12:00:00 AMPPASS
01/29/97 315 - 09&53 ok jf 15rms 1a/c 200a u/g new
ELE96-04226 INSP - Final1/29/19971/29/19971/29/1997 12:00:00 AMPNR
01/29/97 315 - nr jf
ELE96-04227 INSP - Final1/29/19971/29/19971/29/1997 12:00:00 AMPPASS
01/29/97 315 - 14 ok jf sur. posted shall install D.W. & range hood