Inspections for the day of: Wednesday, January 29, 2003.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00263 INSP-Sprinkler Rough-in/Hydro1/28/20031/29/20031/29/2003 12:00:00 AMAPART
###-####. Sprinkler piping is ok to cover from the west side fire doors all the way to the end of the building except for the west elevator lobby. One storage room and a cleaner storage room have sprinkler heads that are over spaced and several hangers need to be added. These locations are marked on the approved sprinkler drawings. 1/29/2003 10:27:22 AM
MIS02-00213 FIR-Final1/28/20031/29/20031/29/2003 12:00:00 AMAPASS
fire life safety and fire sprinkler finaled 1/29/2003 12:21:56 PM
BLD02-02753 FIRE-Final Inspection1/29/20031/29/20031/29/2003 12:00:00 AMPFAIL
Phone #: ###-#### Provide fire dept. plan review notes. Plug pendant that is above ceiling. Provide lever hardware on the five doors in the remodeled area 1/29/2003 1:32:09 PM
FIR02-00414 INSP-Alarm Testing1/28/20031/29/20031/29/2003 12:00:00 AMPFAIL
Retest nitrogen pressure switch, IR detector alarm comes in as a supervisory, loss of power to tool comes in as a supervisory but should be a trouble, loss of power to the IR detector comes in as a supervisory instead of a trouble, These items and the items on the review notes NOT marked with an OK need to be tested 1/29/2003 4:35:19 PM 1/29/2003 4:40:13 PM