BLD07-02823
| FIRE-Final Inspection | 1/29/2008 | 1/29/2008 | 1/29/2008 4:32:24 PM | P | FAIL |
|
|
I stopped at the job site twice. The business is not open today. No inspection performed.
|
FIR08-00023
| INSP-Final Inspection | 1/29/2008 | 1/29/2008 | 1/29/2008 4:31:41 PM | P | FAIL |
|
|
I stopped at the job site twice. The business is not open today. No inspection performed.
|
BLD07-01201
| FIRE-Final Inspection | 1/29/2008 | 1/29/2008 | 1/29/2008 3:39:20 PM | P | PART |
|
|
The insulation at 10346 and 10352 has passed inspection.
|
FIR07-00874
| INSP-Sprinkler Rough-in | 1/28/2008 | 1/29/2008 | 1/29/2008 2:54:44 PM | P | PART |
|
|
The rough-in for the piping in the south wing matches the as-built plans except for the two starter pieces for the branchlines at the building connection. Plans indicate 2" starter pieces but the size installed is 1 1/2". The tenting is not complete yet.
|
BLD07-01845
| FIRE-Conference | 1/29/2008 | 1/29/2008 | 1/29/2008 2:52:47 PM | P | DONE |
|
|
While performing a fire sprinkler inspection I noticed that the backboxes and wire for the fire alarm system had been installed. I posted a stop work order for the fire alarm system and also noted that no covering of walls or ceiling was to be performed. I notified the electrical forman, fire alarm vendor and the job site superintendant. The stop work order was issued due to the fire alarm plans not even being submitted yet per the fire alarm vendor, Sentry Security Systems.
|
BLD07-03101
| FIRE-Final Inspection | 1/29/2008 | 1/29/2008 | 1/29/2008 2:48:34 PM | P | PASS |
|
|
Life safety passed.
|
BLD07-03101
| FIRE-Sprinkler Rough-in | 1/29/2008 | 1/29/2008 | 1/29/2008 2:47:48 PM | P | PASS |
|
|
Fire sprinkler permit passed
|
BLD07-03101
| FIRE-Alarm Testing | 1/29/2008 | 1/29/2008 | 1/29/2008 2:47:02 PM | P | PASS |
|
|
Fire alarm permit passed.
|
FIR08-00020
| INSP-Final Inspection | 1/29/2008 | 1/29/2008 | 1/29/2008 2:45:33 PM | P | PASS |
|
|
Permit finaled. The additional pendant has been added.
|
BLD08-00090
| FIRE-Final Inspection | 1/29/2008 | 1/29/2008 | 1/29/2008 11:46:33 AM | P | FAIL |
|
|
Relocate the new exit discharge light to the main exit instead of around the corner. The other items have been corrected
|
BLD07-02645
| FIRE-Final Inspection | 1/28/2008 | 1/29/2008 | 1/29/2008 11:04:08 AM | A | PASS |
|
|
Life safety passed.
|