FIR08-00759
| INSP-Final Inspection | 1/29/2009 | 1/29/2009 | 1/29/2009 5:06:24 PM | P | FAIL |
|
|
Three pendent heads at the meat dept. do not match response type with adjacent heads in the same fire area, also noted two heads to be adjusted to meet min. spacing req. Remainder of work scope completed okay.
|
FIR07-01051
| INSP-Sprinkler Rough-in | 1/28/2009 | 1/29/2009 | 1/29/2009 5:03:35 PM | P | PART |
|
|
Hangers at the locker room areas okayed for cover, 1st floor classroom wings east and south sides as marked on plans also okayed for cover, noted one missing ssu under the NE stairway and a pendent head at the "time out" room to be changed to an intermediate temp. due to proximity to a heat register.
|
FIR08-00782
| INSP-Final Inspection | 1/28/2009 | 1/29/2009 | 1/29/2009 3:21:33 PM | A | PASS |
|
|
Fire alarm testing passed, record of completion signed, permit finaled.
|
FIR08-00826
| INSP-Conference | 1/29/2009 | 1/29/2009 | 1/29/2009 3:20:05 PM | A | DONE |
|
|
Regarding site inspection schedule.
|
BLD08-01430
| FIRE-Final Inspection | 1/28/2009 | 1/29/2009 | 1/29/2009 3:19:30 PM | A | FAIL |
|
|
Three existing fire extinguishers are two years overdue annual certification, missing building address numbers, one exit sign at the sales area per stamped plan set needs to be added.
|
FIR08-00671
| INSP-Final Inspection | 1/28/2009 | 1/29/2009 | 1/29/2009 3:17:05 PM | A | PASS |
|
|
Fire sprinkler permit work passed final site inspection, contractor to provide missing "911" sign at the outside bell as discussed- to be verified prior to building final.
|
FIR08-00567
| INSP-Sprinkler Rough-in/Hydro | 1/28/2009 | 1/29/2009 | 1/29/2009 3:14:29 PM | A | FAIL |
|
|
New sidewall head at the stairway landing is installed beyond the lowest dimension below the deck per head listing, added upright at the storage room does not match response type or temp. with the adjacent head in the same fire area.
|
FIR08-00766
| INSP-Sprinkler Rough-in/Hydro | 1/28/2009 | 1/29/2009 | 1/29/2009 3:09:49 PM | A | PART |
|
|
Thrust blocking at two 45 deg. ells at the SE corner of the building are approved for cover.
|
FIR06-00901
| INSP-Conference | 1/28/2009 | 1/29/2009 | | A | |
|
|
|