Inspections for the day of: Thursday, January 29, 2009.
Number of inspections: 9
Percentage of inspections complete: 89 %
Percentage of inspections not complete: 11 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00759 INSP-Final Inspection1/29/20091/29/20091/29/2009 5:06:24 PMPFAIL
Three pendent heads at the meat dept. do not match response type with adjacent heads in the same fire area, also noted two heads to be adjusted to meet min. spacing req. Remainder of work scope completed okay.
FIR07-01051 INSP-Sprinkler Rough-in1/28/20091/29/20091/29/2009 5:03:35 PMPPART
Hangers at the locker room areas okayed for cover, 1st floor classroom wings east and south sides as marked on plans also okayed for cover, noted one missing ssu under the NE stairway and a pendent head at the "time out" room to be changed to an intermediate temp. due to proximity to a heat register.
FIR08-00782 INSP-Final Inspection1/28/20091/29/20091/29/2009 3:21:33 PMAPASS
Fire alarm testing passed, record of completion signed, permit finaled.
FIR08-00826 INSP-Conference1/29/20091/29/20091/29/2009 3:20:05 PMADONE
Regarding site inspection schedule.
BLD08-01430 FIRE-Final Inspection1/28/20091/29/20091/29/2009 3:19:30 PMAFAIL
Three existing fire extinguishers are two years overdue annual certification, missing building address numbers, one exit sign at the sales area per stamped plan set needs to be added.
FIR08-00671 INSP-Final Inspection1/28/20091/29/20091/29/2009 3:17:05 PMAPASS
Fire sprinkler permit work passed final site inspection, contractor to provide missing "911" sign at the outside bell as discussed- to be verified prior to building final.
FIR08-00567 INSP-Sprinkler Rough-in/Hydro1/28/20091/29/20091/29/2009 3:14:29 PMAFAIL
New sidewall head at the stairway landing is installed beyond the lowest dimension below the deck per head listing, added upright at the storage room does not match response type or temp. with the adjacent head in the same fire area.
FIR08-00766 INSP-Sprinkler Rough-in/Hydro1/28/20091/29/20091/29/2009 3:09:49 PMAPART
Thrust blocking at two 45 deg. ells at the SE corner of the building are approved for cover.
FIR06-00901 INSP-Conference1/28/20091/29/2009 A