Inspections for the day of: Tuesday, January 29, 2013.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00001 INSP-Final Inspection1/29/20131/29/20131/29/2013 3:44:44 PMPFAIL
All fire pump devices were retested today and passed. Started to test the elevator recall and found that there are programing issues. We tried to test duct smoke detectors but found that some have not been wired for shutdown of the hvac units. Inspection to be rescheduled when the remaining items, as listed above, have been corrected and tested.
BLD12-02789 FIRE-Final Inspection1/28/20131/29/20131/29/2013 3:27:44 PMAFAIL
John and I went over the life safety requirements. Three exit doors need to be provided with single action hardware and all exit signs and emergency lights need to be repaired and tested. I received clarification from Carl Westfall that exit discharge lights are not required and that the exising fire doors are not required either. Fire extinguisher placement is ok. Gate has 20'-0" clearance. Address is installed in two locations.
BLD12-01216 FIRE-Final Inspection1/29/20131/29/20131/29/2013 3:07:17 PMPPASS
Life safety passed
BLD11-03007 FIRE-Final Inspection1/29/20131/29/20131/29/2013 3:02:24 PMPPASS
Life safety passed
BLD12-00857 FIRE-Conference1/28/20131/29/20131/29/2013 1:27:00 PMADONE
Went over sprinkler and fire extinguisher requirements with ED.
BLD12-02829 FIRE-Conference1/28/20131/29/20131/29/2013 11:02:39 AMADONE
I let Brian know that the remote annunciator will need to be relocated to be within the same room as the fire alarm control panel and that a permit will be required for the work. This was verified by the plan reviewer.
BLD12-02491 FIRE-Final Inspection1/29/20131/29/20131/29/2013 10:48:18 AMPPASS
Life safety passed
FIR13-00033 INSP-Final Inspection1/28/20131/29/20131/29/2013 10:10:27 AMAFAIL
Project needed a rough to cover not a final inspection. One pendant as shown on the plans to be relocated did not get relocated as required. Also the new walls are wood which creates a problem with combustibles in a concealed space. Don and I talked about a couple of different options.