Inspections for the day of: Tuesday, January 29, 2013.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00021 Final1/28/20131/29/20131/29/2013 2:25:22 PMPFAIL
Please call Kyle @ ###-#### with questions. Phone #: ###-#### >> Inspection requested via web by Amie Rose NEC 210.62 At least one receptacle outlet shall be installed within 18 in. of the top of a show window for each 12 linear ft. KO seals, panel directorys
ELE13-00159 Final1/29/20131/29/20131/29/2013 1:34:14 PMPPASS
This is for hooking up a buffet table. the owner will be there. Thanks Phone #: ###-#### >> Inspection requested via web by Ron Zimmerman UL listed equipment final ok
ELE13-00154 Electrical Rough-In1/29/20131/29/20131/29/2013 1:17:57 PMPPASS
call Art with questions Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack rough-in ok cover
ELE13-00163 Final1/29/20131/29/20131/29/2013 11:08:44 AMPNR
robert Phone #: ###-#### Not ready for final at this time.
ELE13-00163 Permanent Service1/29/20131/29/20131/29/2013 11:07:48 AMAPASS
p/s u/g rec ok
ELE13-00137 Electrical Rough-In1/29/20131/29/20131/29/2013 10:29:32 AMAPASS
Phone #: ###-#### >> Inspection requested via web by fred lopez corection done rough-in ok cover
ELE13-00183 Rough-In Permanent Service1/28/20131/29/20131/29/2013 10:01:34 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman rough-in p/s u/g n ok
ELE13-00179 Electrical Rough-In1/28/20131/29/20131/29/2013 9:47:00 AMAPASS
Added a switch and an outlet in the new bathroom. After 9:00 am the door will be open. The suite is The Walker Center. Phone #: ###-#### >> Inspection requested via web by Greg Idsinga rough-in ok cover
ELE13-00130 Final1/28/20131/29/20131/29/2013 9:46:07 AMAFAIL
After 9 AM - Virgil Phone #: ###-#### NEC 358.30 Shall secure EMT within 3 ft of termination point. NEC 511.12 All 15 and 20 ampere 120 volt recepectacles installed in commerial garages shall have GFCI protection NEC 408.4 need to label panel directory
ELE12-01410 Electrical Rough-In1/25/20131/29/20131/29/2013 8:59:57 AMAPASS
Contact: Clay Freinwald Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok 2 rooms as highlighted and dated on plans
ELE13-00166 Rough-In Permanent Service1/28/20131/29/20131/29/2013 8:15:15 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Joe Thomas r/i p/s u/g n ok