FIR13-00694
| INSP-Sprinkler Rough-in | 1/29/2014 | 1/29/2014 | 1/29/2014 3:57:24 PM | P | PART |
|
|
Inspection for cover at areas as marked on plans completed- refer to dated annotations on stamped drawings. Noted two overspaced heads, be aware of possible light fixture obstructions due to surface mounted lights not yet installed.
|
FIR13-00695
| INSP-Final Inspection | 1/29/2014 | 1/29/2014 | 1/29/2014 3:52:25 PM | P | PASS |
|
|
Fire alarm field test passed. Permit finaled.
|
FIR14-00040
| INSP-Final Inspection | 1/29/2014 | 1/29/2014 | 1/29/2014 3:51:10 PM | P | PASS |
|
|
Fire alarm work passed functional testing. Permit final approved.
|
FIR13-00644
| INSP-Final Inspection | 1/28/2014 | 1/29/2014 | 1/29/2014 1:41:18 PM | A | PASS |
|
|
Fire sprinkler permit final approved.
|
FIR13-00644
| INSP-Sprinkler Rough-in | 1/29/2014 | 1/29/2014 | 1/29/2014 1:40:42 PM | P | PART |
|
|
Overhead modifications okayed for cover.
|
BLD13-02459
| FIRE-Final Inspection | 1/28/2014 | 1/29/2014 | 1/29/2014 1:39:23 PM | A | PART |
|
|
Need to relocate one emergency light in the vicinity of the exit door equipped with the mag lock hardware per IFC requirements.
|