BLD14-00948
| FIRE-Final Inspection | 1/29/2015 | 1/29/2015 | 1/29/2015 3:26:14 PM | P | FAIL |
|
|
Need all small documents, need the 20' fire dept access clearance around the entire building as per the approved plans, need signage on the electrical room, need the existing "No Parking Fire Lane" signs replaced due to weathering.
|
FIR14-00916
| INSP-Sprinkler Rough-in | 1/29/2015 | 1/29/2015 | 1/29/2015 3:06:32 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR14-00924
| INSP-Final Inspection | 1/28/2015 | 1/29/2015 | 1/29/2015 3:05:14 PM | A | PASS |
|
|
Permit finaled
|
FIR15-00018
| INSP-Final Inspection | 1/28/2015 | 1/29/2015 | 1/29/2015 3:04:45 PM | A | FAIL |
|
|
Outside alarm bell did not ring upon activation of the dry pipe system.
|
FIR14-00745
| INSP-Final Inspection | 1/28/2015 | 1/29/2015 | 1/29/2015 3:04:04 PM | A | FAIL |
|
|
Outside alarm bell did not ring upon activation of the dry pipe system.
|
FIR14-00518
| INSP-Final Inspection | 1/29/2015 | 1/29/2015 | 1/29/2015 3:03:22 PM | A | FAIL |
|
|
We were only able to test one duct smoke detector due to not being able to get the remaining hvac units to function. I noted that the smoke detectors for the fire door release do not appear to be installed per NFPA 80 and Chapter 17 of NFPA 72
|