Inspections for the day of: Monday, January 29, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-00331 Permanent Service1/28/20181/29/20181/29/2018 3:28:22 PMPFAIL
Phone #: ###-#### Inspection requested via web by Don Conley...highiest breaker in panel to center of the grip of the operating handle of circuit breaker is not more than 6' 7" above the floor or working platform....404.8
ELE18-00331 Electrical Rough-In1/29/20181/29/20181/29/2018 3:16:54 PMPPASS
Phone #: ###-#### Inspection requested via web by Don Conley...new wiring for garage...junction boxes in ceiling...new wiring only in garage
ELE17-03748 Final1/29/20181/29/20181/29/2018 2:47:34 PMPNH
Phone #: ###-#### Inspection requested via web by michael hunt...no one home..no access...must reschedule final
ELE17-03432 Final1/28/20181/29/20181/29/2018 2:23:10 PMPPASS
Phone #: ###-#### Inspection requested via web by Mark Morgan...job complete...ok to final
ELE17-02988 Final1/29/20181/29/20181/29/2018 1:54:31 PMPFAIL
Phone #: ###-#### Inspection requested via web by Kurtis Boller...
1..outlets in pantry shall be on the small appliance circuit...210.52(B)(1)...verify
2..plate on switches in new bathroom needs replaced...move box..110.3
3..outlet in closet needs to be GFI protected..within 6' of shower...210.8(A)
4..all outlets and devices in bedrooms shall have AFCI protection...switch patio lights..210.12
5..outlets on island are not to code...210.52(C)(5)
ELE18-00266 Final1/26/20181/29/20181/29/2018 11:50:58 AMAPASS
Please call Aaron for access information ###-####. General Contractor on the job Shane ###-####. Thank You!! Phone #: ###-#### Inspection requested via web by Clay Morgan...replacement/upgrade exit signs and co2 detector added..ok
ELE10-02472 ELE-Aging Inspection1/29/20181/29/20181/29/2018 10:16:25 AM DONE
unable to get ahold of homeowner to verify if any work was done
ELE17-04057 Final1/28/20181/29/20181/29/2018 10:14:13 AMAPASS
Phone #: ###-#### Inspection requested via web by Steve Craig...corrections made...ok to final
ELE17-03802 Final1/26/20181/29/20181/29/2018 9:04:22 AMAPASS
Access code is 4888 Phone #: ###-#### Inspection requested via web by Paula Gratiot...corrections made...ok to final
ELE17-02963 Final1/26/20181/29/20181/29/2018 8:22:55 AMANR
Lock box code 8068. If you have any questions please feel free to contact Aaron ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clay Morgan...scheduled by accident...not ready
ELE18-00043 Final1/26/20181/29/20181/26/2018 4:50:46 PMACANC
Please lock door when finished Phone #: ###-#### >> Inspection requested via web by danny perrine Inspection cancelled from web by: danny perrine