ELE03-00006
| Electrical Rough-In | 1/2/2003 | 1/3/2003 | 1/3/2003 12:00:00 AM | A | NR |
|
|
RON; Phone #: ###-#### Internet Inspection Request from: Darla Downs met contractor at job site 1/3/2003 12:17:45 PM
|
ELE02-03393
| Final | 1/2/2003 | 1/3/2003 | 1/3/2003 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 01/02/2003 at 15:09:58. Contact: ###-####. ok 1/3/2003 11:59:20 AM
|
ELE02-03976
| Electrical Rough-In | 1/2/2003 | 1/3/2003 | 1/3/2003 12:00:00 AM | A | PASS |
|
|
###-#### john r/i basement ok 1/3/2003 11:12:05 AM
|
ELE02-02740
| Final | 1/3/2003 | 1/3/2003 | 1/3/2003 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 01/03/2003 at 08:53:29. Contact: ###-####. shall not ID #6 or smaller equip grd, shhall be green if insulated250.119 called 1/3/2003 3:36:55 PM
|
ELE02-03331
| Final | 1/3/2003 | 1/3/2003 | 1/3/2003 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 01/03/2003 at 10:58:17. Contact: ###-####. cor. met with contractor, 680.8 needs proper clearence over spa and deck area 22.5 ft ,and 250.24 a grounding electrode conductor shall be installed from service to u/g water system 1/3/2003 2:44:12 PM
|